3.1.2

GT23

Item
*1
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistant
Operating atmosphere
*3
Operating altitude
Installation location
*4
Overvoltage category
*5
Pollution degree
Cooling method
Grounding
*1
Includes the temperature inside the enclosure of the control panel on which the GOT is installed.
*2
If the ambient temperature exceeds 40 °C, the absolute humidity must not exceed 90% RH at 40 °C.
*3
Do not use or store the GOT under a pressure higher than the atmospheric pressure at altitude 0 m.
Doing so may cause a malfunction.
Air purging by applying pressure to the control panel may create clearance between the surface sheet and the touch panel. This
may cause the touch panel to be not sensitive enough or the sheet to come off.
*4
This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical
power distribution network and the machinery within the premises.
Category II applies to equipment that is supplied with power from fixed facilities.
The withstand surge voltage for the equipment with the rated voltage up to 300 V is 2500 V.
*5
This indicates the occurrence rate of conductive material in an environment where a device is used. Pollution degree 2 indicates
an environment where only non-conductive pollution occurs normally and a temporary conductivity caused by condensation shall
be expected depending on the conditions.
Under
Compliant with
intermittent
JIS B 3502 and
vibration
IEC 61131-2
Under
continuous
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147 m/s
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust,
Grounding with a ground resistance of 100 Ω or less.
If impossible, connect the ground cable to the control panel.
Specifications
0 °C to 55 °C
-20 °C to 60 °C
10% RH to 90% RH, non-condensing
10% RH to 90% RH, non-condensing
Frequency
Acceleration
5 to 8.4 Hz
-
2
8.4 to 150 Hz
9.8 m/s
5 to 8.4Hz
-
2
8.4 to 150 Hz
4.9 m/s
2
(15G), 3 times in each X, Y, or Z direction)
and direct sunlight (as well as at storage)
2000 m or less
Inside control panel
II or less
2 or less
Self-cooling
3.1 General Specifications
*2
*2
Half amplitude
Sweep count
3.5 mm
10 times in each
X, Y, or Z
-
direction
1.75 mm
-
-
3 - 3
3