SYSTEM COMPONENTS
3.1
Wiring Diagram
The XR150/XR550 Series diagram below shows some of the accessory modules you can connect for use in various
applications. A brief description of each module follows in section 3.3.
AC Wiring must be in conduit and exit
out the left side of the enclosure.
Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.
¼"
The plug-in transformer shall plug
into a 120VAC 60 Hz outlet not
controlled by a switch and all 16
to 18 gauge wire shall run
through conduit.
Bell
12VDC
Minimum cutoff time 5 min.
1.5 Amp Max
3.2
Lightning Protection
Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on panel input and output
circuits. Additional surge protection is available by installing the DMP 370 or 370RJ Lightning Suppressors
Network Transient Suppression Module .
Digital Monitoring Products
4
System Components
Power
LED
J3
Phone Line
XR550 Series
Panel
Outputs 3-6
Battery
Start
s
s
AC
AC
+B
–B
BELL GND
RED YEL GRN BLK
1
2
3
4
5
6
7
8
s
16 to 18 gauge wire
s
Maximum AC Wire distance
s
s
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
RED
BLACK
s
s
Earth
Cold Water
Ground
Ground
Pipe Earth
Ground
1k
Ohm
Bell
Bell cutoff time
range is 5 to 99
minutes, non-coded.
Keyswitch Arming
can be connected
to any zone.
s
s
s
s
s
s
s
s
s
s
s
Smoke
DISARM
Detector
ARM
1k Ohm 1k Ohm 1k Ohm
1k Ohm
Figure 1: XR550 Series Wiring Diagram
Form C Relays (J2)
Output Color Code–Model 431 Harness
Output 2
N/O
Orange/White
Output 2
Com White/Gray
Output 2
N/C
Violet/White
s
Output 1
N/O
Orange
Output 1
Com Gray
Output 1
N/C
Violet
Annunciator Outputs (J11)
Output Color Code
Output 3
Red
Output 4
Yellow
Output 5
Green
Output 6
Black
J11
Output 1
Output 2
J2
K6
K7
J13
J10
J4
Tamper
J8
J14
J9
J15
J17
PROG
SMK GND
Z1
GND
Z2 Z3
GND
Z4 Z5
GND
9
10
11
12 13
14
15 16
17
18 19
20
S
S
S
S
S
S
S
S
S
S
S
1k
1k
1k
1k
1k
1k
Ohm
Ohm
Ohm
Ohm
Ohm
Ohm
Auxiliary/Smoke Power
Total current combined from terminals 7, 11, 25,
27, XBUS and LX500-LX900:
s
s s
1.5 Amp Max 13.8VDC to 10.2VDC
BLACK
GREEN
YELLOW
RED
RED
YELLOW
GREEN
BLACK
s
s
Zone Expander
Zone
Model 714
Expander
7mA @ 12VDC
Model 711
Models 714-8, 714-16
7mA @
20mA @ 12VDC
12VDC
S
S
S
S
S
S
1k Ohm 1k Ohm 1k Ohm
1k Ohm
Intended Installation Environment - Indoor/Dry
WARNING: Incorrect connections
may cause damage to the unit.
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM VERIFICATION FEATURE THAT
RESULTS IN DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS.
THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60
SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS
UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
Front and Rear tamper
s
protection included
s
with Model 350A
Attack Resistant
Link LED
Activity LED
Enclosure.
s
J1
Ethernet
Front
Tamper
Tamper
J18
Any other contact
J6
Load
devices listed for Fire
Protective Signaling can
be connected to zones
J16
9 and 10.
Reset
Zones 9 and 10 and
J24
Model 715 compatibility
Cell Module
identifier: A
Maximum operating
range: 13.8VDC to
J19
Class B (Style A).
Using verification delays
on zones 9 and 10 is
Z6 Z7
GND
Z8 Z9+ Z9– Z10+ Z10–
optional. Use the
delays marked on the
smoke detectors.
21 22
23
24 25 26
27
28
Zone
Zone
9
10
S
S
S
S
S
1k
1k
Ohm
Ohm
s
= Supervised Circuit
S
S
S
S
3.3k
3.3k
Ohm
Ohm
Resistor
Resistor
Card Reader
RED
Zone Expander
Model 715
7mA @ 12VDC
Models 715-8, 715-16
20mA @ 12VDC
Zone Expander
(up to 8 zones)
Model 712-8
S
S
S
S
S
19mA @
12VDC
3.3k Ohm 3.3k Ohm 3.3k Ohm 3.3k Ohm
S
S
S
S
1k Ohm
Listed Resistors
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308
CAUTION: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE RUN TO
PROVIDE SUPERVISION OF CONNECTIONS.
WARNING
or Model 270
XR150/XR550 Series Installation Guide
Rear
9.7VDC.
S
S
S