242
Fieldbus Communication
Pos: 109.25 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/MODBUS-Register (x41) - Teil 1.0 (0x1000 bis 0x102A) @ 3\mod_1235399979343_21.doc @ 27603 @ 3 @ 1
12.2.5
MODBUS Registers
Table 130: MODBUS registers
Register
address
0x1000
0x1001
0x1002
0x1003
0x1004
0x1005
0x1006
0x1007
0x1008
0x1009
0x100A
0x100B
0x1020
0x1021
0x1022
0x1023
0x1024
0x1025
0x1028
0x1029
0x102A
Pos: 109.26 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/MODBUS-Register (750-880, -881, -352) - Teil 1.1 (0x102B) @ 7\mod_1265628629284_21.doc @ 49988 @ @ 1
0x102B
Pos: 109.27 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/MODBUS-Register (x41) - Teil 1.1 (0x1030 und 0x1031) @ 7\mod_1265628290879_21.doc @ 49982 @ @ 1
0x1030
0x1031
Pos: 109.28 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/MODBUS-Register (750-880, -881) - Teil 1.1 (0x1035 bis 0x1037) @ 7\mod_1265628768490_21.doc @ 49991 @ @ 1
0x1035
0x1036
0x1037
Pos: 109.29 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/MODBUS-Register (x41) - Teil 1.2 (0x1050) @ 7\mod_1265628337132_21.doc @ 49985 @ @ 1
0x1050
Pos: 109.30 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/MODBUS-Register (x41) - Teil 3 @ 3\mod_1235460292328_21.doc @ 27613 @ @ 1
0x2000
0x2001
0x2002
0x2003
0x2004
0x2005
0x2006
0x2007
0x2008
0x2010
0x2011
0x2012
0x2013
0x2014
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Access Length
Description
(Word)
R/W
1
Watchdog time read/write
R/W
1
Watchdog coding mask 1...16
R/W
1
Watchdog coding mask 17...32
R/W
1
Watchdog trigger
R
1
Minimum trigger time
R/W
1
Watchdog stop (Write sequence 0xAAAA, 0x5555)
R
1
Watchdog status
R/W
1
Restart watchdog (Write sequence 0x1)
R/W
1
Stop watchdog (Write sequence 0x55AA or 0xAA55)
R/W
1
MODBUS and HTTP close at watchdog time-out
R/W
1
Watchdog configuration
W
1
Save watchdog parameter
R
1...2
LED error code
R
1
LED error argument
R
1...4
Number of analog output data in the process image (in bits)
R
1...3
Number of analog input data in the process image (in bits)
R
1...2
Number of digital output data in the process image (in bits)
R
1...4
Number of digital input data in the process image (in bits)
R/W
1
Boot configuration
R
9
MODBUS/TCP statistics
R
1
Number of TCP connections
W
1
KBUS Reset
R/W
1
Configuration MODBUS/TCP time-out
R
3
Read out the MAC-ID of the coupler/controller
R/W
1
Timeoffset RTC
R/W
1
Daylight Saving
R/W
1
Modbus Response Delay (ms)
R
3
Diagnosis of the connected I/O modules
R
1
Constant 0x0000
R
1
Constant 0xFFFF
R
1
Constant 0x1234
R
1
Constant 0xAAAA
R
1
Constant 0x5555
R
1
Constant 0x7FFF
R
1
Constant 0x8000
R
1
Constant 0x3FFF
R
1
Constant 0x4000
R
1
Firmware version
R
1
Series code
R
1
Coupler/controller code
R
1
Firmware version major revision
R
1
Firmware version minor revision
WAGO-I/O-SYSTEM 750
Manual
Version 1.0.1
Need help?
Do you have a question about the 750-880 and is the answer not in the manual?
Questions and answers