Chapter 1 Site Requirements

When planning the installation of your OfficeServ500 system, choose a site that meets the following
requirements.
There is sufficient space for easy installation
(Figure
1–1) and adequate lighting.
The location minimizes cable lengths. (See the Cable Requirements table in Chapter 3, "Specifica-
tions", of the Samsung OfficeServ500 General Description guide.)
The equipment should not be exposed to direct sunlight, corrosive fumes, dust, constant vibration or
strong magnetic fields such as those generated by motors and copy machines.
A direct commercial AC power outlet is required. Do not use extension cords. Preferably, a dedicated
circuit should be used to minimize the risk of other electrical equipment being connected that could
adversely affect system operation.
Ensure that all wires and cables going to and coming from the system are properly routed. Do not
cross fluorescent lights or run parallel with AC wires.
The equipment must be located in an environment that will maintain a temperature range of 32°~77°F
(0°~25°C) and a humidity range of 10%~90% non-condensing.
This equipment is to be installed only in Restricted Access Areas (e.g. dedicated equipment rooms,
equipment closets).
Allow at least 25cm (10") clearance on both sides and above the system to ensure proper ventilation
and access to the interior of the cabinet.
Do not install in close proximity to a fire sprinkler head or to other sources of water.
Space consideration must be made to allow floor or wall mounting. Do not wall mount a multiple cabi-
net system.
Meeting these requirements will help to ensure proper performance and greater life expectancy of the
system.