6 System Commissioning and Functions
◆ Independent Running
The independent running function is described as follows:
● The elevator responds to only car calls; it does not respond to hall calls, and the registered hall
call is cleared automatically.
● The elevator does not close the door automatically. You need to hold down the door close button
to close the door. During door close, if you release the door close button, the elevator opens the
door again automatically.
● If the elevator is under parallel/group control, it exits the parallel/group control system after
entering the independent running state.
● Set FE-32 Bit9 to 1, and perform independent running signal input via JP23 on the MCTC-
CCB-A.
◆ Fire Emergency Running
The fire emergency function is described as follows:
● The elevator clears car calls and hall calls automatically.
The elevator stops at the nearest floor without opening the door, and then directly runs to the fire
●
emergency floor.
● The elevator keeps the door open after arriving at the fire emergency floor.
6
● If the elevator is under parallel/group control, it exits the parallel/group control system after
entering the fire emergency running state.
Note that the preceding description is the default setting of the system, and certain actions can be modified
by setting the related parameters.
The firefighter function is described as follows:
● The elevator does not respond to hall calls. It responds to only the car call and only one car call
can be registered.
● The elevator does not open or close the door automatically. You need to press the door open/
close button (jog) to open/close the door.
● The light curtain signal input is inactive, and the safety edge signal input is active.
Note that the preceding description is the default setting of the system, and certain actions can be modified
by setting the related parameters.
The input and output setting of fire emergency running and firefighter running is as follows:
1.
Input setting:
●
Generally, the fire emergency signal is input via the fire emergency switch on the HCB of
any floor, and the firefighter signal is input via JP24 on the CCB. If these signals need to be
input via the MCB, perform parameter setting (takes input terminal Xa and Xb as an example)
according to the following table.
- 136 -
new
NICE3000
User Manual
Need help?
Do you have a question about the nice3000 and is the answer not in the manual?
Questions and answers
عندي لوحة يظهر في الشاشة رقم 8 فقط في وسط الشاشة ولايتحكم في أي شئ
New Fuji elevator with monarch drive The door operator open signal light doesn't come on
The door operator open signal light may not come on for the Monarch NICE3000 drive in the new Fuji elevator due to one or more of the following reasons:
1. Opposite Door Function Mode: If the system is in opposite door control mode, the door open signal function is only enabled in mode 2 (hall call independent, opposite-door manual control). If the system is not configured correctly for this mode, the signal may not activate.
2. Input Configuration (JP16/IP16): If JP16 or IP16 inputs are not correctly set, the system may not recognize the correct door (front or back) to open, preventing the open signal from activating.
3. Door Lock Signal Issue: If the door lock signal is invalid or the door and hall door are in different states, the system may block the door open signal.
4. Elevator Lock Signal Active: If the elevator lock signal is active, the elevator will not respond to calls, and no door open signal will be generated.
5. Fault Conditions: Certain faults like motor overheat (Err39) or communication failure (E57) can prevent normal operation, including door opening.
6. Door Open Limit Signal Not Detected: If the door open limit signal is not properly detected (E55), the system may not allow the door to open.
Check these conditions and signals to determine the cause.