Operation
6.5 Local operation
Operating functions
Notice
Zero point calibration
For absolute pressure transmitters, the zero point is at vacuum.
A zero point calibration with transmitters which do not measure absolute pressure leads to
faulty settings.
Table 6-4
Operating functions via keys
Function
Measured value
Zero point (only with
"Pressure"
measurement type)
Limit point (only with
"Pressure"
measurement type)
Electrical damping
Zero point in so-called
blind adjustment
Limit point in so-called
blind adjustment
Zero point calibration
(position correction)
Current sensor
Output current in case
of fault
6-10
Mode
Key function
<MODE> <UP>
<DOWN> <UP> and
The
modes
are
selected
here.
2
Current
Current
higher
lower
3
Current
Current
higher
lower
4
Damping
Damping
higher
lower
5
Pressure
Pressure
higher
lower
6
Pressure
Pressure
higher
lower
7
Correctio
Correctio
n value
n value
higher
lower
8
Current
Current
higher
lower
9
Switching between
lower fault current
and upper fault
current.
Display, explanations
<DOWN>
The current measured value is displayed as
you have adjusted it in the "Measured value
display, mode 13" function.
Set to 4 mA
Output current in mA
Set to 20 mA
Output current in mA
Set to 0
Time constant T63 in seconds
Adjustment range: 0.0 s to 100.0 s
Setting zero
Zero point in the selected pressure unit
point to 0
Setting limit
Limit point in the selected pressure unit
point to upper
measuring
limit
Performing
Pressurizing transmitter for gauge pressure
or level
Evacuating transmitter for absolute pressure
(< 0.1% of the span).
(Zero point remains unaffected)
Measured value in pressure unit
Switching on
constant output current in mA
"3.6"; "4", "12", "20" or "22.8"
Switch off with the <MODE> key.
lower fault
selected output current possible: Fault
current
current limits adjusted by user
Operating Instructions, 06/2005, A5E00359579-02
SITRANS P300 with HART communication