ABB Freelance 2000 Manual page 44

Operator station configuration
Table of Contents

Advertisement

Section B
Play sound files in In addition to the sound files configured here for the various priorities,
Pause between
two messages
Area filter
Sound board
Relay board
The relay card itself must be installed in Windows on the DigiVis PC. The program
DigiVis Configure offers the option of installing driver software for the relay card. For
further information see also also Operators Manual, Operator Station, DigiVis Instal-
lation, Modifying Installation.
Gross Automation, 1725 South Johnson Road, New Berlin, WI 53146, www.ssacsales.com, 800-349-5827
B-26
sound files can also be configured for individual process messages. The
following three alternatives can be used to control their processing under
DigiVis:
Priority order, oldest message,
Priority order, newest message,
Time order
Priority-controlled: the sound file for the most important message
is repeated until such time as the message is acknowledged or super-
ceded by a more important message.
Time-controlled: The sound files of all coming messages are played
back once each in the order in which the messages arise.
See also Operators Manual, Operator Station, Messages and Hints,
Messages with sound files.
The minimal interval interposed between sound files for different mes-
sages or between repetitions of the same sound file for a particular mes-
sage.
Determines, from which areas messages control the control room horn.
The sound system of the DigiVis PC is active.
The sound system of the DigiVis PC is inactive. Configured sound files
will not be played.
The relay board of the DigiVis PC is active.
The relay board of the DigiVis PC is inactive. Configured relay termi-
nals will not stetted.
Messages and Hints

Hide quick links:

Advertisement