Start/Stop
Automatic
Event controlled
Tag name of event
function block
Manual
Filing
in .. files
named
Number of cycles
Cycle time
Disk space req.
for this log:
Gross Automation, 1725 South Johnson Road, New Berlin, WI 53146, www.ssacsales.com, 800-349-5827
E-22
Logging is automatically started by starting DigiVis.
Logging is started and stopped by an event.
Name of event starting logging,
see Engineering Reference Manual, Functions and Function Blocks,
Monitoring Function Blocks.
Press the function key F2 to bring up a selection list.
The operator can start and stop logging on the operator station. This refers
only to the log previously selected on the operator station.
specifies the number of log files, which are created on DigiVis PC. The
value must be between 1 and 400.
the name of the log file, which is filed on DigiVis PC hard disk. The preset
name can be accepted, or a new one given.
With the start of logging, the data is written cyclically to the file according to
the entered cycle time. The range of values lies between 1 and 32767.
This field specifies the interval between two recordings. Entries are made in
the IEC 1131-3 format. The value range is between 0 and 2147483 sec.
Example:
T#2147483s or T#24d20h31m23s.
The recording time in a file is calculated from the number of cycles x
cycle time.
The size which log files can attain is displayed in this field. This requirement
should be available on DigiVis PC.