Mitsubishi Electric MELSEC Q Series User Manual page 52

Safety programmable controller
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

5
SETTINGS AND PROCEDURES BEFORE
OPERATION
Number
1)
Indicator LED
CC-Link part, extension communication part
2)
terminal block
3)
Module power supply part terminal block
4)
Safety input part terminal block
Safety power supply, start-up
5)
part terminal block
6)
Safety output part terminal block
CC-Link transmission speed
7)
terminating resistor setting
switch
CC-Link station number setting
8)
switch
9)
Start-up mode setting switch
10)
Safety part extension connector OUT
11)
Serial number display
Table 5.2 Part names (1/2)
Name
Indicates status of safety output Z.
Z
ON:
OFF:
X0
Indicates status of safety input (X0, X1).
ON:
X1
OFF:
Indicates operating status of the internal safety relay K0 (coil status of K0).
K0
ON:
OFF:
Indicates operating status of the internal safety relay K1 (coil status of K1).
K1
ON:
OFF:
DA, DB, DG: Data terminal for CC-Link cable
SLD: Shielding wire terminal of CC-Link cable
EA, EB, EG: Data terminal for extension communication
EP: Power supply terminal for extension module
+ 24V: Module power supply + 24V terminal
24G: Module power supply 24G terminal
X0: Safety input X0 input terminal
COM: Safety input X0 COM terminal
X0, X1
X1: Safety input X1 input terminal
COM: Safety input X1 COM terminal
XS0, XS1: Start-up off check terminal
XS
+ 24V: Safety power supply + 24V terminal
24G: Safety power supply 24G terminal
Z00, Z01: Safety relay output terminal
Z10, Z11: Safety relay output terminal
Z20, Z21: Safety relay output terminal
A switch for setting transmission speed of the CC-Link system and if
terminating resistor is attached to the CC-Link system or not
•Transmission speed setting (Switch number from 1 to 3)
1 to 4
•Setting if CC-Link terminating resistor is attached or not (Switch number 4)
Setting switch LT
ON: Terminating resistor is attached.
OFF: Terminating resistor is not attached.
A switch for setting the station number of CC-Link system
•Set tens place of the station number with "
STATION No.
•Set ones place of the station number with "
Set a station number within the range from 1 to 64.
(Repeat use of a station number is not possible.)
A switch for setting start-up mode
"A" side: Auto mode
"M" side: Manual mode
A connector for connecting an extension module
A serial number same as the one shown on the rating plate
Description
Safety output is generated (both K0 and K1 are ON).
Safety output is not generated.
Safety output is generated.
Safety output is not generated.
Operating status of the internal safety relay K0 is ON.
Operating status of the internal safety relay K0 is OFF.
Operating status of the internal safety relay K1 is ON.
Operating status of the internal safety relay K1 is OFF.
Setting switch status (B RATE)
Setting
4
2
0
OFF
OFF
1
OFF
OFF
2
OFF
ON
3
OFF
ON
4
ON
OFF
Set the transmission speed within the range from 0 to 4.
5.2 CC-Link Safety Relay Module
5.2.3 Part names and settings
Transmission
speed
1
OFF
156kbps
ON
625kbps
OFF
2.5Mbps
ON
5Mbps
OFF
10Mbps
10" of "STATION No.".
1" of "STATION No.".
5
- 10
1
2
3
4
5
6