16 Installation (Electric) and Service Instructions
4
Connecting to external equipment
(1) External system inputs
(no-voltage contact point static)
DI 1
All stop input
DI 2
All start input
(reserved)
DI 3
Keep the input and output signal line lengths to under 20 meters. For distances greater
than this, install a standalone communication adaptor, or use a relay.
For use in areas that may be susceptible to electrical noise, use two-conductor
shielded cable (with one line grounded), with a cross-section of 0.5 mm
Do not apply external voltages to the input terminals.
The input terminals use a sensing current of about 10 mA at 5 V DC.
The output terminal allowable contact voltage and current are 30 V DC, 0.5 A.
5
Power switch
The Intelligent Controller has a power switch.If the
LCD is blank after connecting power, check the
position of the power switch.
Power
supply
terminals
POWER
Power
switch
OFF
Verify the system confi guration, make necessary settings
7
1 Turn on power to all air conditioner units.
2 Turn on power to the Intelligent Controller.
3 Set the date and time on the Intelligent Controller and verify the system confi guration.
4 Following the display on the Intelligent Controller, verify the number of units connected.
5 Perform the necessary settings. Be sure to set the central control address.
* See the Operation Manual for details.
Educating the customer
8
 Give the Operation Manual to the customer.
 Explain the operation to the customer, following the explanations given in the Operation Manual.
(2) External system outputs
(no-voltage contact point static)
Equipment
(Output common)
All alarm output
All operation output
ON
Equipment
2
or greater.
Circuit board diagram
6
Home key
S
6
HOME
Termination resistor
jumper for
communication
adaptor control wire
S1
100-240V~
1
3
CN1
Power supply
P
o
w
r e
s
w
c t i
h
terminals
* Ordinarily, there is no need to change any settings on the Intelligent
Controller board.
99
(3) Pulse meter inputs
(no-voltage contact point pulse)
P1
P2
P3
*1 Factory default setting (alterable)
Minimum pulse width 100 msec
Minimum pulse interval 1 sec
7-segment LED
Up / down /set keys
D1
S7
S8
S
9
D2
UP DOWN SET
CN2
10
0
Gas flow meter
(Fuel flow meter)
*1
Electricity meter 1
Electricity meter 2
19
9
S
g i
n
a
t l
r e
m
n i
a
s l