EN-82 SMTP Service
Option:
[0] *
Disable
[1]
Enable
EN-89 Transparent Socket Channel Port
Range:
0*
[0 – 9999]
EN-90 Cable Diagnostics
Option:
[0] *
Disable
[1]
Enable
NB!
The cable diagnostics function will only be issued on ports where there is no link (see par. EN-10, Link Status)
EN-91 Auto Cross-Over
Option:
[0]
Disable
[1] *
Enable
NB!
Disabling of the auto cross-over function will require crossed Ethernet cables for daisy-chaining the options.
EN-92 IGMP Snooping
Option:
[0]
Disable
[1] *
Enable
EN-93 Cable Error Length
Option:
[0]
Error length Port 1 (0 – 200m)
[1]
Error length Port 2 (0 – 200m)
Function:
Disables the SMTP (e-mail) service on the option.
Enables the SMTP (e-mail) service on the option.
Function:
Configures the TCP port-number for the transparent socket channel. This enables Drive-messages to be
sent transparently on Ethernet via TCP. Default value is 4000, 0 means disabled.
Function:
Enables/disables advanced Cable diagnosis function. If enabled, the distance to cable errors can be read
out in par. EN-93. The parameter resumes to the default setting of Disable after the diagnostics have
finished.
Function:
Disables the auto cross-over function.
Enables the auto cross-over function.
Function:
This prevents flooding of the Ethernet protocol stack by only forwarding multicast packets to ports that
are a member of the multicast group
Disables the IGMP snooping function.
Enables the IGMP snooping function.
Function:
If Cable Diagnostics is enabled in par. EN-90, the built-in switch is able via Time Domain Reflectometry
(TDR). This is a measurement technique which detects common cabling problems such as open circuits,
short circuits and impedance mismatches or breaks in transmission cables. The distance from the option
to the error is displayed in meters with an accuracy of +/- 2m. The value 0 means no errors detected.
Modbus TCP
6