O-04 Control Word Timeout Function
Select the time-out function. The time-out function activates when the control word fails to be updated within the time period specified in par. O-03 Control
Word Timeout Time.
Option:
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
6
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
NB!
The following configuration is required in order to change the set-up after a time-out:
Set par. K-10 Active Set-up to [9] Multi set-up and select the relevant link in par. K-12 This Set-up Linked to.
O-05 End-of-Timeout Function
Option:
[0]
Hold set-up
[1] *
Resume set-up
O-06 Reset Control Word Timeout
This parameter is active only when Hold set-up [0] has been selected in par. O-05 End-of-Timeout Function.
Option:
[0] *
Do not reset
[1]
Do reset
34
Function:
Resumes control via serial bus (Network or standard) using the most recent control word.
Freezes output frequency until communication resumes.
Stops with auto restart when communication resumes.
Runs the motor at JOG frequency until communication resumes.
Runs the motor at maximum frequency until communication resumes.
Stops the motor, then resets the frequency converter in order to restart: via the network, via the reset
button on the Keypad or via a digital input.
Changes the set-up upon reestablishment of communication following a control word time-out. If com-
munication resumes causing the time-out situation to disappear, par. O-05 End-of-Timeout Function de-
fines whether to resume the set-up used before the time-out or to retain the set-up endorsed by the time-
out function.
See [7] Select setup 1
See [7] Select setup 1
See [7] Select setup 1
Function:
Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].
Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until
par. O-06 Reset Control Word Timeout toggles. Then the drive resumes its original set-up.
Resumes the set-up active prior to the time-out.
Function:
Retains the set-up specified in par. O-04 Control Word Timeout Function, following a control word time-
out.
Returns the frequency converter to the original set-up following a control word time-out. The frequency
converter performs the reset and then immediately reverts to the Do not reset [0] setting