(2) Strength and surface material of free-access floor panels
Table 2.3
panels.

Table 2.3 Strengths and surface materials of free-access floor panels

Floor-panel strength
Surface
material
(3) Opening for server-system-use
That area of the free-access floor in which a server system is installed requires a floor
panel opening, an auxiliary support and a slit floor panel.
When Fujitsu receives a free-access floor allocation plan from the user after the
finalization of an equipment layout, it will furnish an opening diagram marked with
an opening pattern, an auxiliary support position, and a slit floor panel position.
The user then proceeds with construction of the floor panel opening, an auxiliary
support, and slit floor panel on the basis of this opening diagram.
a) Floor panel opening
That area of the free-access floor in which an equipment is installed must have an
opening in the floor panel to facilitate equipment cabling and underfloor cold
ventilation.
b) Auxiliary supports
Depending on the shape of the floor panel opening, an auxiliary support may be
required to augment panel strength and to secure the panel in a firm position. In
installing equipment, such as a magnetic tape unit, on a floor panel, an auxiliary
support should be used to reinforce the floor panel so that the equipment can be kept
level by offsetting panel deflection.
c) Slit floor panels
Depending on the heat dissipation and the air intake/exhaust structures of the
equipment installed, a slit floor panel for cold ventilation may have to be installed in
the service area.
C120-H007-08EN
lists the strengths and surface materials suggested for free-access floor
Item
Deflection not exceeding 1.5 mm (0.05 in.) under a
concentrated load of 4.9 kN (1100 lbf)
Suppression of
Volume resistivity falling 10
static electricity
Oil resistance and
Resistant to oils used during maintenance and easy to clean
ease of cleaning
Dust buildup
Resistant to dust buildup
characteristics
2.3 Computer Room Structure
Condition
to 10
6
9
19