Perform ZONE TEST (Test mode)
(H7)
Up to 100 zones can be set in test mode, which is indicated by the
LED "Test mode" on the front.
When an alarm point in a zone set in test mode is tested, it is presented
in the display as a fire alarm but with the information "Test mode"
added. If a printer is available the test mode alarm will be printed
with the information "(test mode)" added.
The LEDs "Fire" will be blinking (like for a fire alarm) but no outputs
will be activated except the fire door outputs. The test mode alarm
will be automatically reset after approx. 10 seconds.
Press the Soft key "Menu".
With the keypad select 0, 1, 2 - - 8 or 9 for a User name.
Type the Password for that user name. (Six digits. * * * * * *)
H1 Perform monthly test
Press (  ) six times to highlight menu H7.
H7 Perform ZONE TEST
Press ( ).
Set in test mode
By default is Zone 000.
Use the keypad to type a zone number.
➐ Press ( ).
A successful zone in test mode is indicated by a beep and a
will also be shown in the End test mode list
A not successful zone in test mode is indicated by another beep and a
"X".
Up to 100 zones can be in test mode.
➑ Perform the tests.
End test mode
➒ Press the Soft key
Set in test mode
End test mode
❿ Scroll in the list with (  ) or (  ) and select.
EBL512 G3 version 2.0.x, Daily user's manual