(3) Thermistor (Liquid and gas piping temperature detection)
Procedure
1. Remove the service panel
1 Use the procedure under (1)-1.2 to check TH11,
TH12, and TH15.
2 Use the procedure under (1)-1.2.3 to check TH13
and TH14.
2. Disconnect the piping sensor lead from the control-
ler panel.
1 TH11 - TH14 (CN10)
2 TH15, TH16 (CN11)
3. Pull the temperature sensor from the temperature
sensor housing and replace it with a new sensor.
4. Connect the temperature sensor lead securely to
the controller board.
(4) Pressure Sensor
Procedure
1. Remove the sensor panel.
1 Use the procedure under (1)-1.2 to check PS1
and PS3.
2. Disconnect the connector of the applicable pressure
sensor from the controller board and insulate the
connector.
1 Liquid pressure sensor (CNP1)
2 Intermediate pressure sensor (CNP3)
3. Install a new pressure sensor at the location shown
in the photograph, and plug the connector into the
controller board.
Important
1 In the case of gas leakage from the pressure sen-
sor, take actions to fix the leak before performing
the above procedure.
Be careful when removing heavy parts.
TH15
TH15
TH14
TH13
CMB-P1010V-D
TH15 TH11 TH12
TH16
CMB-P1016V-E
PS3
PS1
CMB-P1010V-D
PS1
PS3
CMB-P1016V-E
–125–
Photos
TH12
TH13
TH14
Photos