Shot2 to Shot5 for CB#1 –settings (TD_MS2, TRR2 and others)
(xi)
The ARC1 logic for shot 2-shot5 is illustrated in Figure 2.24-20. Shots 2-5 are applicable for a
CB#1 only. For example, two shots (Shot2 and Shot3, i.e., [ARC_NUM]=S3) are required
following the Shot1, the user should set the [TS_MS2]/[TS_MS3] and [TRR2]/[TRR3]. The user
should program to inject a permission signal for the Shot2 and Shot3 at PLC connection points
'ARC1-S2 COND' and 'ARC1-S3 COND', as shown in Figure 2.24-20. Note that the CB will be
tripped in three-phases forcibly even if a GEN.TRIP-A (TRIP COMMAND-A) signal is only
generated, because the 'CB1_BRIDGE' signal is generated during the Shot 2-Shot5.
Initiation
ARC1 IN-PROG
Shot counter
SHOT_2ND
SHOT_3RD
SHOT_4TH
SHOT_5TH
≥1
Shot number
ARC-NUM
Done issuing ARC1 SHOT2
A
Done issuing ARC1 SHOT3
B
C
Done issuing ARC1 SHOT4
Done issuing ARC1 SHOT5
D
810001EBC9
ARC1-S2 COND
810001EBCA
ARC1-S3 COND
810001EBCB
ARC1-S4 COND
810001EBCC
ARC1-S5 COND
ARC1-S2
S
&
IN-PROG
R
ARC1-S3
S
&
IN-PROG
R
S
&
ARC1-S4
R
IN-PROG
S
&
R
ARC1-S5
IN-PROG
8100011B67
8100011B68
8100011B69
8100011B6A
Figure 2.24-20 ARC1 logic for Shot2 to Shot5
- 367 -
TD_MS2
8100011B67
t
0
ARC1 SHOT2
&
0.01 – 300.00 s
TD_MS3
t
0
8200011B68
&
ARC1 SHOT3
0.01 – 300.00 s
TD_MS4
8300011B69
t
0
ARC1 SHOT4
&
0.01 – 300.00 s
TD_MS5
8400011B6A
t
0
ARC1 SHOT5
&
0.01 – 300.00 s
TRR2
t
0
ARC1-S2 TRR
0.01 – 310.00 s
TRR3
t
0
ARC1-S3 TRR
0.01 – 310.00 s
TRR 4
t
0
ARC1-S4 TRR
0.01 – 310.00 s
TRR 5
t
0
ARC1-S5 TRR
0.01 – 310.00 s
8800011B62
Shot2–Shot5 for CB#1
GRZ200 (Soft 031 & 032)
6F2S1915 (0.46)
Issuing
A
B
C
D
To TRC
ARC1 FT
CB1_94TT
ARC1 FT
CB1_94TT
ARC1 FT
CB1_94TT
ARC1 FT
CB1_94TT
CB1_BRIDGE