FRQ trip signal
(iii)
The FRQ can issue a trip signal for the function of trip circuit (TRC) when Trip is set for scheme
switch [FRQ1-UseFor]. However, when an alarm signal is required in place of the trip signal,
the user should set Alarm for scheme switch [FRQ1-UseFor]. The TRC function is discussed
separately. (See Chapter
UF/OF scheme logic
(iv)
Figure 2.17-2 shows the scheme logic for the UF and OF functions. Each stage operates
independently. PLC connection point "FRQ1-BLOCK" is provided to block the stage1 when
blocking is required by an external signal. The user can connect the PLC connection point with
an external signal using PLC function. (For more information of PLC function, see Chapter
PLC function
)
The under-voltage block (FRQBLK) element is used to block the FRQ operation, as
mentioned earlier (section 2.17.1(i)).
8700001C23
FRQBLK
1
(UVBLK)
&
OF
FRQ1
1
UF
&
OverFrq
UnderFrq
FRQ1-Chara
&
OF
FRQ2
1
UF
&
OverFrq
UnderFrq
FRQ2-Chara
&
OF
FRQ6
1
UF
&
OverFrq
UnderFrq
FRQ6-Chara
On
FRQ1-EN
On
FRQ2-EN
On
FRQ6-EN
1
800001EBB0 FRQ1-BLOCK
1
810002EBB0 FRQ2-BLOCK
1
850006EBB0 FRQ6-BLOCK
Relay application: Trip circuit
8000011C23
TFRQ1
t
0
≥1
&
&
0.00 - 300.00s
8100021C23
TFRQ2
t
0
≥1
&
&
0.00 - 300.00s
8500061C23
TFRQ6
t
0
≥1
&
&
0.00 - 300.00s
Figure 2.17-2 Scheme logic for FRQ function
- 280 -
.)
8000011BB1
8000011B60
800001EBB1 FRQ-S1-OPT
Trip
FRQ1-UseFor
Alarm
8100021BB1
8100021B60
810002EBB1 FRQ-S2-OPT
Trip
FRQ2-UseFor
Alarm
8500061BB1
8500061B60
850006EBB1 FRQ-S6-OPT
Trip
FRQ6-UseFor
Alarm
6F2S1915 (0.46)
NON FRQBLK
FRQ-S1-OPT
&
≥1
FRQ-OPT-TRIP
&
FRQ-OPT-ALARM
FRQ-ARC-BLOCK
FRQ-S2-OPT
&
&
FRQ-S6-OPT
&
≥1
&
GRZ200 (Soft 031 & 032)
To DFRQ
To TRC