Diagnostics
3.1 Diagnostics via LEDs
Control Unit 320-2 DP in operation
Table 3- 4
Control Unit CU320-2 DP – Description of the LEDs after booting
LED
Color
RDY
(READY)
Green
Red
Red/
green
Orange
Green/
orange
or
red/
orange
DP
PROFIdrive
cyclic
operation
Green
Red
240
State
Description, cause
OFF
Electronic power supply is missing or outside
permissible tolerance range.
Continuous
The component is ready for operation and cyclic
light
DRIVE-CLiQ communication is taking place.
Flashing light
Commissioning/reset
0.5 Hz
Flashing light
Writing to the memory card
2 Hz
Flashing light
General errors
2 Hz
Flashing light
Control Unit is ready for operation.
0.5 Hz
However, there are no software licenses.
Flashing light
Updating the firmware of the DRIVE-CLiQ
0.5 Hz
components
Flashing light
DRIVE-CLiQ component firmware update complete.
2 Hz
Wait for POWER ON for the components in
question.
Flashing light
Component detection via LED is activated
2 Hz
(p0124[0]).
Note:
Both options depend on the LED status when
component recognition is activated via p0124[0] = 1.
Off
Cyclic communication has not (yet) taken place.
Note:
PROFIdrive is ready for communication when the
Control Unit is ready (see LED RDY).
Continuous
Cyclic communication is taking place.
light
Flashing light
Full cyclic communication has not yet taken place.
0.5 Hz
Possible causes:
The controller is not transferring any setpoints.
During isochronous operation, no global control
(GC) or a faulty global control (GC) is transferred
by the controller.
Flashing light
PROFIBUS master is sending wrong
0.5 Hz
parameterization/configuration data
Flashing light
Cyclic bus communication has been interrupted or
2 Hz
could not be established
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Remedy
Check power supply
Check parameterization /
configuration data
Obtain licenses
Turn POWER ON for the
components in question
Adapt configuration
between
master/controller and CU
Remedy fault