  • Page 1 USER’S MANUAL MIM-D00 MIM-D00U (Data Management Server) DB98-25059A(1) MIM-Doo_IB_E_25059.indd 2006-03-21 ソタネト 7:34:57...
  • Page 2: Safety Precautions

    Safety Precautions • Before using the DMS, read carefully these instructions. • After reading the instructions, keep this user's manual in a handy and safe place. If a user is changed, you must hand over the manuals. • Never attempt to install the air conditioning system or to move the DMS by yourself. D o not attempt to install or repair this DMS by yourself.
  • Page 3: Table Of Contents

    Contents General Description ................4  NTRODUCTION OF DMS S ..............4  DVANTAGES OF YSTEM Main Function ........... 5  NTERFACE WITH PPER EVEL ONTROLLER .................. 5  RROR ISTORY ................6  ET AND CHEDULE ........6  NTEGRATED OWER ISTRIBUTION...
  • Page 4: General Description

    DMS (D NTRODUCTION OF ANAGEMENT ERVER The DMS is an Internet based device for central management of Samsung system air-conditioners. It supports LAN & WAN and operates 24 hours without a separate PC. DMS S DVANTAGES OF YSTEM The DMS provides the following advantages: ...
  • Page 5: Main Function

    Main Function Interface with Upper Level Controller The DMS receives control data from the upper level controller and sends the received data to the lower level system. The upper level controllers of the DMS are the SNET series and the connectible SNET series are SNET-III, SNET- and SNET mini.
  • Page 6: Set And Run Schedule

    Main Function (Continued) Set and Run Schedule The schedule function of the DMS can be set though the Web or using the upper level controller. Weekly/Yearly schedules can be set and the following information can be assigned to each schedule: Content Item Remark...
  • Page 7: System Architecture

    System Architecture Web Client SNET-III Internet Centralized Up to 8 units Controller Up to 8 units Power meter Power meter  In order to use the power distribution function in the DMS, relevant devices as shown above must be installed. (Consult the installers.) Time Segmentation ...
  • Page 8: Peak Power Control

    Main Function (Continued) Peak Power Control The DMS performs peak power control without a separate PC. Rs 485 Centralized Centralized Controller Controller Peak I/M Demand Power Cable Controller Max 256 Indoors (DVM Series)  In order to use the peak power control function in the DMS, relevant devices as shown above must be installed.
  • Page 9 2) Operation Mode  Peak power control runs in one of the 3 modes: ‘No Control’, ‘Priority Control Mode’ , and ‘Circulation Control Mode. ’  No Control: If the peak power control mode is set to ‘No Control’ , peak power control will not run. The default DMS setting is set to ‘No Control’...
  • Page 10 Main Function (Continued) 3) Restrictions of indoor unit use  If operation mode of an indoor unit is Dry, Cool, and Auto, each indoor unit is converted to Fan mode when peak power control is applied.  If an indoor unit is operated under Heat, run with one operation among change to Fan mode, power off, and set temperature change (16 degree.) It can be set on the upper controller or the Web.
  • Page 11: Sharing Peak Power Control Information With Other Dms

    Sharing Peak Power Control Information with other DMS’  By sharing the peak power control information with other DMS’ , several buildings can be controlled using the peak power control.  This setting consists of one master DMS and several slave DMS’ and the information of the master DMS must be set on all slave DMS’...
  • Page 12: Using The Dms Through The Web

    Using the DMS through the Web Setting the Web Environment nstall JRE 1.3.1 or later version  Java Runtime Environment 1.3.1 or a later version must be installed on the PC. JRE is installed automatically if the PC is connected to the Internet and when the DMS is accessed for the first time.
  • Page 13: Login

    Login Function Details  Login allows only authorized users to access the web page.  There is no limit on the number of users that can access the DMS at the same time, however, less than 5 users are recommended for access speed reasons.
  • Page 14: Monitoring And Control

    Using the DMS through the Web (Continued) Monitoring and Control Function Details  On this screen users can monitor the operation status of all indoor units and control each indoor unit. Only one selected indoor unit can be controlled. Monitoring and Control The status of all indoor units can be viewed from the ‘Monitor all indoor units.
  • Page 15 Select and click on the indoor unit and the background color of the indoor unit is changed to green. The operation status of the selected indoor unit is displayed on the upper part. Displayed items are as follow: Displays the name of the selected indoor unit. Selected indoor unit address Displays whether there is an error on the selected Error...
  • Page 16: View Error History

    Using the DMS through the Web (Continued) View Error History Function Details The DMS users can view and delete error history of the DVM  system. The DMS saves up to 256 errors. Viewing the Error History  All error history can be checked from the ‘View Error History’...
  • Page 17: Set, Run And View Schedule

    Set, Run and View Schedule Function Details Users can set, edit, and delete schedules for controlling the DVM  system. Using the Schedule Function   The Schedule List screen shows all current schedule information saved in the DMS. On the schedule screen, a schedule can be created, edited, viewed, and deleted.
  • Page 18 Using the DMS through the Web (Continued) Viewing the Error History        On the Create New Schedule screen, users can set the Schedule Name, Schedule Period, Applied Indoor Unit, and Event. For the event, users can set the Repeat or not, Day, On Time, Off Time, Temperature, Mode, and Remote Control Allow or not.
  • Page 19 When pressing the ‘Add Event’ button from the , a new  event is added. When pressing the ‘Delete Event’ button from after selecting a check box from the , the selected   event is deleted When pressing the ‘OK’ button from the after setting all ...
  • Page 20: Setting And Viewing Peak Power Control

    Using the DMS through the Web (Continued) Setting and Viewing Peak Power Control Function Details The DMS users can set and view the peak power control information.  Refer to pg. 5~7 for more information on peak power control.  Using Peak Power Control Select the “No Control”...
  • Page 21    S elect one of the three modes in the indoor unit operation    (‘Switch to Fan Mode, ’ ‘Set Heating Temperature to 16, ’ and ‘Power OFF’) T he ‘Priority’ can be set from level 0 to level 3. ...
  • Page 22 Using the DMS through the Web (Continued) Setting the Circulation Control   S elect the ‘Circulation Control’ as shown in the screen above.    C lick on the ‘Edit’ button to set the priorities of each indoor unit as shown in ...
  • Page 23: Peak Power Monitoring

    S elect one of the three modes in the indoor unit operation    (‘Switch to Fan Mode, ’ ‘Set Heating Temperature to 16, ’ and ‘Power OFF’)  T he ‘Circulation Period’ can be set between 3 minutes and 10 minutes. ...
  • Page 24: Setting And Viewing The Power Distribution Function

    Using the DMS through the Web (Continued) Setting and Viewing the Power Distribution Function Function Explanation Users can set, inquire, and edit the information of power  distribution section. Refer to pg. 4 for more information on the Power Distribution ...
  • Page 25   3 Sections are classified into Section A, Section B, and Section C. The setting method is same as 2 sections’ setting method.   MIM-Doo_IB_E_25059.indd 2006-03-21 ソタネト 7:34:54...
  • Page 26: Inquire Power Distribution Result

    Using the DMS through the Web (Continued) Inquire Power Distribution Result Function Explanation Users can inquire operation breakdowns and power usage by  indoor units that is saved in the DMS. Inquiring the result      Total Indoor units (by period) Select ‘Total Indoor units (by period)’...
  • Page 27       Individual Indoor unit (by period) Select ‘Individual indoor units (by date)’ in to check the  power consumption and the running rate by date for individual indoor unit. Select the indoor unit to check in ...
  • Page 28: Setting And Viewing The System Environment

    Using the DMS through the Web (Continued) Setting and Viewing the System Environment Function Explanation The DMS users can set and view information related to the DMS  system installation and operation. (The installer must complete the system environment setup when installing the DMS.) System environment setup MIM-Doo_IB_E_25059.indd 2006-03-21...
  • Page 29 DMS Network Information Change the set information by inquiring the existing set network information from the DMS network information and clicking the Edit button. If this information is changed, the DMS is restarted automatically. Master DMS Information Master/Slave is a setting for sharing of time and peak power control information when several DMS are connected to the one system.
  • Page 30: Tracking

    Using the DMS through the Web (Continued) Tracking Function Details Tracking is the most initial stage that a DMS recognizes the DVM indoor/outdoor units.  When performing a Tracking, some information may be lost; thus, use with care. User can order the Retry of a Tracking and mange the name of devices on the Tracking information screen.
  • Page 31: User Management

    User Management Function Explanation You can manage users to access the Web. By using this menu, you  can add, edit, and delete users though the Web.    When accessing this page, you can see the current registered user list.
  • Page 32: Terms

    Terms   The abbreviation of Data Management Server.   PPER ONTROLLER It means SNET Series, a local controller of the DVM system. S-Net i and SNET III are linked to a DMS.   ENTRALIZED ONTROLLER A device that controls 16 groups of the DVM air conditioner. A central control device of a DVM system which is located between a DMS and an outdoor unit transmitter.