Items Required; Procedure; Fan Status Leds - HP AA-RWF3A-TE Installation Manual

Hewlett-packard san switch installation guide
Table of Contents

Advertisement

Table 20
describes the Fan Status LEDs and provides corrective actions.
Table 20 Fan Status LEDs
LED color
No light
Steady green
Steady amber
for more than 5
seconds

Items required

Replacing a 4/64 SAN Switch fan assembly takes approximately two minutes and
requires the following items:
New fan assembly
Phillips #1 screwdriver

Procedure

To replace a fan assembly in a 4/64 SAN Switch:
1.
Unscrew the captive screw on the fan assembly using a Phillips screwdriver.
2.
Remove the fan assembly from the chassis by pulling the handle out away from the
chassis.
3.
Orient the new fan assembly as shown in
screw on the left.
4.
Gently push the new fan assembly into the chassis until it is firmly seated.
5.
Secure the fan assembly to the chassis by tightening the captive screw.
104
Installing field-replaceable units
Meaning
Fan assembly is not receiving power.
Fan assembly is operating normally.
Fan fault for one of the following reasons:
One or more of the fans in the fan assembly
has failed.
The fan FRU was disabled by the user.
Corrective action
Verify that the fan assembly is seated in the
switch.
No action required.
Verify that the fan FRU is enabled. If the fan
FRU is enabled, it is faulty and should be
replaced.
Figure 36
on page 105, with the captive