DC Output Module

Feature
Outputs
Isolation
Operating Voltage
Output type
Peak Voltage
On-State Voltage drop
Overload Protection
Maximum Load Current
Maximum Leakage Current
Maximum In-rush Current
Minimum Load
Base Power Required
Response Time
Fuses
Revision 5
9/03
16 (current sinking, low side)
2 groups of 8 outputs/group
6.5 to 32 Vdc (5.0 to 6.5 V @ < 0.5 A per channel)
Intelligent Power Switch (IPS)
34Vdc
0.3 Vdc @ 1 A load
Electronic high-current and high temperature limiting, resets after cycling field
power
1 A per point, 8 A max. per card, resistive load
0.15 mA @ 32 Vdc
4 A for 10 ms
0.0 mA
426 mA @ 5 V
Off to On: 10 ms
On to Off: 5 ms
Electronic limiting
HC900 Hybrid Controller Installation and User Guide
Specifications - DC Output Module