Installer System-Test - Honeywell DELUXEHEATPUMP T8511G Installation Instructions Manual

Deluxe heat pump zone thermostat
Hide thumbs Also See for DELUXEHEATPUMP T8511G:
Table of Contents

Advertisement

T8511G DELUXE HEAT PUMP ZONE THERMOSTAT
IMPORTANT
Review the settings to confirm that they match
the system. To exit the Installer Setup, press and
hold the Information i key until the display
returns to normal (approximately three seconds).

INSTALLER SYSTEM-TEST

Use the Installer System-Test to check the thermostat
operation. Refer to Table 3 for a list of the available
system-tests.
To start the system-test:
CAUTION
The minimum off time for compressors is bypassed
during the Installer System-Test. Equipment damage
can occur if the compressor is cycled too quickly.
Press and hold the increase
the same time, until two zeros appear. All segments of the
LCD will be displayed before the two zeros appear. See
Fig. 11 and 12.
Table 3. Tests Available In the Installer System-Test.
Test
Number
System-Test Description
10-19
Heating equipment can be turned on
and off
20-29
Emergency heat (select models)
equipment can be turned on and off
30-39
Cooling equipment can be turned on
and off
40-49
Fan equipment can be turned on and off
60-69
Keyboard keys test
70-79
Thermostat information including date
code and software versions are displayed
Key to
Test
Press
Number
Heating Equipment System-Test
i
10
11
12
11
10
Emergency Heating Equipment System-Test (select models)
i
20
21
20
Cooling Equipment System-Test
i
30
31
30
69-1052—1
and decrease
keys at
Table 4. Installer System-Test Options.
Enter heating equipment system-test.
Stage-one heat comes on. System fan is also energized.
Stage-two heat comes on. Stage-one heat and system fan remain on.
Stage-two heat turns off.
Stage-one heat and system fan turn off.
Changing from heating to emergency heating equipment system-test.
Emergency heat comes on. System fan also comes on.
Emergency heat turns off.
Change from heating or emergency heating to cooling equipment system-test.
Cool and system fan come on.
Cool and system fan turn off.
Em Ht Temporary Setting
Aux Ht
Repl
Wait
Batt
System
Em HeatOffCool Auto Only
Fig. 11. Display of all the segments of the LCD.
TEST MODE NUMBER
Fig. 12. Display of test number.
Refer to Table 4 for the directions and results of the
specific tests.
NOTE: Press and hold the increase
keys together for three seconds to exit the
system-test. The system-test will time out after
ten minutes without any key presses.