Honeywell DELUXEHEATPUMP T8511G Installation Instructions Manual page 5

Deluxe heat pump zone thermostat
Hide thumbs Also See for DELUXEHEATPUMP T8511G:
Table of Contents

Advertisement

Installer Setup
Number
(Press i key
to change)
Select
Not used
01 thru 04
Heating cycle
rate
Not used
08 thru 11
Changeover
Not used
Degree tempera-
ture display
Not used
15 thru 18
Extended fan
operation in
heating
Extended fan
operation in
cooling
Not used
21 thru 23
Outdoor
temperature
a
display
Not used
25 thru 32
Minimum off time
for the
compressor
Heating setpoint
a
range stop
Cooling setpoint
a
range stop
System on
indicator
(flame=heat,
snowflake=cool)
a
is displayed
Temperature
display
adjustment
a
Available on select models.
Table 2. Thermostat Installer Setup Options.
Factory Setting
Display
05
06
Stage 2
06
Not used
07
06
Emergency heat
12
01
Manual changeover
13
14
00
Temperature is
displayed in °F
19
00
No extended fan
operation after the
call for heat ends
20
00
No extended fan
operation after the
call for cool ends
24
00
No outdoor
temperature is
displayed
33
05
5 minute minimum off
time for the
compressor
34
90
Heating setpoint can
be set no higher than
90°F
35
48
Cooling setpoint can
be set no lower than
48°F
36
00
LCD On symbol is
displayed when
system is energized
37
00
No difference in
displayed
temperature and
actual room
temperature
T8511G DELUXE HEAT PUMP ZONE THERMOSTAT
(Press
Description
Display
03, 06
or 09
00 or
02
01
01
01
01
00, 01,
02, 03
or 04
40 thru
90
48 thru
99
01
-3 thru
03
5
Other Choices
or
key to change)
Description
03—3 cph used for hot water
systems
06—6 cph used for heat pump
systems
09—9 cph used for electric heat
systems
00—Automatic changeover
02—Auto only
Temperature is displayed
in °C
Fan operation is extended
90 seconds after the call for
heat ends
Fan operation is extended
90 seconds after the call for
cool ends
Outdoor temperature is
displayed. Needs a C7089B1000
Outdoor Sensor to operate.
Minimum number of minutes
(0 thru 5) the compressor will be
off between calls for the
compressor
Number can be set anywhere
between 40 and 90 in 1°F
increments
Number can be set anywhere
between 48 and 99 in 1°F
increments
Display is disabled
01—Display adjusts to 1°F higher
than actual room temperature
02—Display adjusts to 2°F higher
than actual room temperature
03—Display adjusts to 3°F higher
than actual room temperature
-1—Display adjusts to 1°F lower
than actual room temperature
-2—Display adjusts to 2°F lower
than actual room temperature
-3—Display adjusts to 3°F lower
than actual room temperature
Actual
Setting
69-1052—1