2.2.12 Modbus command group

The modbus command group controls the Modbus TCP slave functionality.
Command
Parameters
modbus_key
[key]
mb_tcp_enable
on|off
mb_slave_id
[id]
mb_tcp_port
[port]
mb_float_enable
on|off

2.2.13 Events command group

The events command group controls the alarm notification via traps and/or e-mail.
Command
Parameters
showevents
event
[row] [e-mail] [trap] [en]
NOTE: When the specific alarm handling is disabled, the alarm occurrence will be totally filtered – the
alarm will never appear active, it will not be reported by any mean and it will not be logged.
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V014.doc
Description
Enter the license key to enable Modbus TCP feature
[key]
License key in GUID format
Note: Modbus TCP support requires a license key.
Refer to the Modbus section of this manual for details
Enable Modbus TCP slave
on
Modbus TCP slave enabled
off
Modbus TCP slave disabled
Set Modbus TCP Slave ID
[id]
1..247 = Set Modbus TCP Slave ID
255
= Disables Slave ID check
Set the Modbus TCP Port to be used
[port] TCP port to be used for Modbus TCP
Note: Default port for Modbus TCP is 502
Enable floating-point handling
on
Floating-point handling enabled
off
Floating point handling disabled
Note: A non-standard floating-point representation is
used – refer to the Modbus section of this manual for
details.
Description
Show the alarm notification configuration
Configure the alarm notification for a specific event
[row]
Alarm ID
[e-mail] 0 = no e-mail notification for this alarm
1 = send e-mail on alarm (de)activation
[trap]
0 = no trap sent for this alarm
1 = send trap on alarm (de)activation
[en]
0 = alarm handling disabled
1 = alarm handling enabled