Metering - GE 400 User Manual

Sg series 400 & 500 kva / 480vac ul / s2
Hide thumbs Also See for 400:
Table of Contents

Advertisement

6.2

METERING

The METERING mode is entered any time the "METER" button is pressed.
The LCD screen will indicate a series of screenshots showing the measures of all electric parameters like
AC, DC and various statistics.
In this mode the buttons perform the following functions:
Return to HOME screen.
Scrolls backward to the previous screen.
Scrolls forward to the next screen.
It is possible to view any pushbutton functional description by pushing the button for more than 3
seconds.
Home\Meter
BATTERY
V
I
T
Charge level
Autonomy
Home\Meter
RECTIFIER
f
:
60.0 Hz
L12
:
480 V
L23
:
480 V
L31
:
480 V
Home\Meter
UTILITY
f
L1
L2
L3
BYPASS FREE
Modifications reserved
OPM_SGS_USM_M40_M50_2US_V010.doc
545 V
100.0 A
+25° C
80 %
12 Min
Vdc
:
540 V
Idc1
:
250.0 A
Idc2
:
250.0 A
60 Hz
275 V
279 V
276 V
Battery data screen
V
The battery voltage.
I
The battery current (negative values correspond to
the discharge of the battery).
T
The temperature of the battery ("SENSOR DISABLE"
indicates sensor disabled).
Charge level
The battery charge level.
Autonomy
The estimated backup time with the
present load.
Rectifier utility data screen
f
The input frequency of the rectifier.
L12
L23
The voltage levels between the three phases (line-
L31
to-line).
Vdc
Rectifier voltage output.
Idc1
Output current 1
st
Idc2
Output current 2
nd
Bypass utility data screen
f
The frequency of the utility.
L1
L2
3-phase utility voltage PHASE /NEUTRAL.
L3
Bypass
Bypass status: FREE / LOCKED.
Rectifier bridge.
Rectifier bridge.
User Manual SG Series 400 & 500 UL S2
Page 25/79