Led 1; Led 4A Led 4B Led - GE 400 User Manual

Sg series 400 & 500 kva / 480vac ul / s2
Hide thumbs Also See for 400:
Table of Contents

Advertisement

SG Series
S2
500
Fig. 6.1-2 LEDs on Synoptic Diagram
Examples of typical scenarios in the Synoptic Diagram:
Load supplied by Inverter
Load supplied by Battery
Modifications reserved
OPM_SGS_USM_M40_M50_2US_V010.doc
UPS Model
Battery level LED
All lightning lit LED open indicate a battery autonomy of 100%.
LED A
Fixed:
Blinking:
LED A, B
Indicate a battery autonomy between 26% and 50%.
LED A, B, C
Indicate a battery autonomy between 51% and 99%.
Min:
Battery autonomy time in minutes estimates with actual load.
Load level LED
All LED Off indicate a load status at ≤25%.
LED A
LED A, B
LED A, B, C
LED A, B, C, D
LED D blinking
UPS series number
indicates a battery autonomy between 6% and 25%.
indicates a battery autonomy ≤5%.
Indicates a load level between 26% and 50%.
Indicate a load level between 51% and 75%.
Indicate a load level between 76% and 100%.
Indicate a load level between 101% and 124%.
Indicates a load level ≥125%.
LEDs on Synoptic Diagram

LED 1

LED 2
LED 3
LED 4a
LED 4b
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
Load supplied by Automatic Bypass
Load supplied by eBoost™ Operation Mode (option)
When the Load is supplied by eBoost™ Operation Mode
the "eBoost" text is displayed.
UPS nominal rating (kVA)
Utility Rectifier OK
Utility Bypass OK
Rectifier ON
Discharging Battery
Charging Battery
Inverter available
Inverter ON
Q1 closed (load on UPS)
Automatic Bypass ON
Manual Bypass Q2 ON
Load on UPS
Page 24/79