Honeywell UDC3300 User Manual page 53

Universal digital controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

Function
Prompt
Lower Display
Control Output Direction
ACTION
Output Change Rate
OUT RATE
Output Rate Up Value
PCT/M UP
PCT/M DN
Output Rate Down Value
High Output Limit
OUTHiLIM
OUTLoLIM
Low Output Limit
High Reset Limit
I HiLIM
Low Reset Limit
I LoLIM
Controller Dropoff Value
DROPOFF
DEADBAND
Output Relay Deadband
Failsafe Mode
FAILMODE
Failsafe Output Value
FAILSAFE
5/00
Function
Name
UDC3300 Expanded Model: DC330E User Manual
Selections or
Range of Setting
Upper Display
DIRECT
REVRSE
ENABLE
DISABL
0 to 9999 % per minute
0 to 9999 % per minute
–5 to 105 % of output
–5 to 105 % of output
Within the range of the output
limits
Within the range of the output
limits
–5 to 105 % of output
–5.0 to 5.0 %
NO LAT
LATCH
Set within the range of the
output limits. 0 to 100 %
Configuration
Factory
Setting
REVRSE
DISABL
0
0
100
0
100.0
0.0
0
1.0
NO LAT
0
43

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Udc330e

Table of Contents