Honeywell UDC3300 User Manual page 101

Universal digital controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

Function
Keyboard Reset
Viewing the
Present Ramp or
Soak Segment
Number and Time
Viewing the
Number of Cycles
Left in the
Program
End Program
Disable Program
5/00
Press
until you see
LOWER
Lower Display: ToBEGN
DISPLAY
Press
LOWER
until you see
Upper Display: "R" and the PV value
DISPLAY
Lower Display: Ramp segments:
# indicates the segment number (Ramp–odd only, Soak–
even only)
XX.XX
Ramp Rate – EU/MIN or EU/HR
Soak Time – Hours.Minutes
LOWER
until you see
Upper Display: "R" and the PV value
DISPLAY
Lower Display: RECYC XX
Number of cycles remaining in the setpoint program.
XX = 0 to 99
When the final segment is completed, the "R" in the upper
display either changes to "H" (if configured for HOLD
state) or disappears (if configured for disable of setpoint
programming).
The controller operates at the last setpoint in the program
in automatic or will be in manual mode at the failsafe
output.
See Section 3.5 for details.
UDC3300 Expanded Model: DC330E User Manual
Setpoint Rate/Ramp/Soak Program Operation
Result
key to reset program to beginning at Hold state.
Soak segments:
Ramp Time – Hours.Minutes
# RA XX.XX
# SK XX.XX
91