Wiring - Honeywell Braukmann F74C Product Data

Reverse rinsing filter and automatic-backwash controls
Hide thumbs Also See for Braukmann F74C:
Table of Contents

Advertisement

Fig. 11. Removing the MV876 cover.
Fig. 12. Installing batteries in the MV876.
Fig. 13. Replacing the MV876 fuse.
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS

WIRING

IMPORTANT
MV876
Mount the 24 Vac transformer and wire as shown in Fig. 14.
Reconnect power to the system. When the system is
powered, the MV876 will run through one backwash cycle
(approximately 20 seconds).
Set MV876 backwash interval to the desired setting. See the
M17352
Operation section.
Check MV876 operation by interrupting primary power to the
transformer. When power is switched back on, the MV876 will
backwash the F74C once.
M17353
M17351
7
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before wiring.
All wiring must comply with applicable codes and
ordinances.
MV876
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
Fig. 14. Wiring diagram for F74C with MV876.
1
L1
(HOT)
L2
M16484
62-3061

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Braukmann mv876

Table of Contents