Addressable Module Mounting - Honeywell HPF24S8 Installation Manual

Field charger/power supply
Hide thumbs Also See for HPF24S8:
Table of Contents

Advertisement

Installation

2.3 Addressable Module Mounting

The HPF24S has been designed to allow the mounting of an addressable control, relay or monitor
module on the main circuit board inside the power supply cabinet with the module status LED
visible through the closed door. This allows power to be fed from the HPF24S Auxiliary Power
output directly to the module, if needed, without running the power wires outside the cabinet. As an
example, Figure 2.5 illustrates wiring from the Auxiliary power output terminals to a FCM-1
control module's terminals 11 (-) and 10 (+).
NOTE: The module mounting kit (P/N 90286) is pre-installed on the power supply main circuit board.
Module Installation
1.
Place addressable module over (4) standoffs and
secure with (4) supplied screws.
2.
Wire module as shown in illustration above.
18
standoff
standoff
standoff
standoff
Figure 2.5 Mounting Module In HPF24S Cabinet
*If the SLC device does not match the one in this figure,
refer to the SLC manual appendix, which contains wiring
conversion charts for type V and type H modules.
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
Addressable Module Mounting