ASPIRATION LOW FLOW
ASPIRATION POWER FAULT
ASPIRATION SCANNER FAULT
ASPIRATION TIME BASE FAULT
BEAM ALIGNMENT MODE ACTIVE
Notifier INSPIRE E10/E15 Control Panels - Commissioning
Meaning and possible remedial action.
If a fault persists then seek advice. Any remedial action requiring wiring
or replacement of parts, this work must be done by a trained engineer.
Aspiration low flow fault detected. This fault relates to
ASD air sampling fire detection equipment. This fault
indicates that the flow of air through the aspirator
is outside the required range for correct operation.
Action: Air flow should be checked and adjustments
made where necessary.
Aspiration detector power fault detected.
Action: Check the supply of power to the ASD detector
and ensure it is present.
Aspiration scanner fault detected.
Action: TBA.
Aspiration time base fault detected.
Action: TBA.
The beam detector is currently in alignment mode (to
allow the transmitter to be aligned with the reflector).
This mode is entered when the Alignment Mode button
(at Access Level 2) on the detector is pressed. There is
no fire cover while in this mode.
Action: If after completion of beam detector
commissioning it is still in this mode this message
indicates the device was not installed correctly and the
set up procedure needs to be carried out again (use the
instructions provided in the device manual).