Honeywell NOTIFIER INSPIRE E10 Commissioning Instructions page 25

Fire alarm control panels
Hide thumbs Also See for NOTIFIER INSPIRE E10:
Table of Contents

Advertisement

Message
EXTERNAL POWER SUPPLY FAULT
HIGH TEMPERATURE FAULT
INTERNAL POWER SUPPLY FAULT
LOW TEMPERATURE FAULT
MAINS SUPPLY FAILED
OVER CURRENT FAULT
Notifier INSPIRE E10/E15 Control Panels - Commissioning
Meaning and possible remedial action.
If a fault persists then seek advice. Any remedial action requiring wiring
or replacement of parts, this work must be done by a trained engineer.
External power supply has a fault.
Action: Check for cause and rectify the fault, follow the
instructions supplied with the external power supply.
The PSU and Charger module are operating under
much higher than normal temperatures.
Action: Check and ensure the panel is installed in a
correct environment and also power is not being used
to power non specified equipment.
TBA
Action: TBA
The PSU and Charger are operating under much lower
than normal temperatures.
Action: Check and ensure the panel is installed in a
specified environment.
Mains supply fault has been detected.
Action: Check the mains fuse in panel and at the fused
spur unit, also check mains voltage to PSU and the
internal wiring.
A current too high fault has been detected.
Action: Monitor and if possible determine what is
taking excessive current. If the fault persists then seek
advice.
25