Power Connection Guidelines for AC-Powered Systems

Power Connection Guidelines for AC-Powered Systems
When connecting AC-input Power Supply Units (PSUs) to the site power source, observe the guidelines
described here.
Warning
• Ensure that the AC-input power supply module has a detachable power cord.
• Each chassis power supply should have a separate, dedicated branch circuit.
• If you are using a 208 or 240 VAC power source in North America, note that such lines are considered
Warning
Warning
Powering on the Router
2
Statement 1028 More Than One Power Supply
This unit might have more than one power supply connection. To reduce risk of electric shock, remove all
connections to de-energize the unit.
• North America
• PSU3.2KW-ACPI only—Power supply modules require a 20 A circuit.
• International—Circuits should be sized according to local and national codes.
hot and the circuit must be protected by a two-pole circuit breaker.
Statement 1005 Circuit Breaker
This product relies on the building's installation for short-circuit (overcurrent)
protection. To reduce risk of electric shock or fire, ensure that the protective
device is rated not greater than:
• 20 A circuit breaker for an AC-input power supply module.
• 50 A DC-rated circuit breaker for each input of a DC-input power supply module, for safety purposes
- irrespective of whether the inputs are power from a single or separate DC sources.
This product requires short-circuit (overcurrent) protection, to be provided as
part of the building installation. Install only in accordance with national and local
wiring regulations. Statement 1045