58
Setting
Descriptions
Value (0)
Specify the name of this digital input when it has a value
Name
of 0.
The name can be entered manually, or double-click this
field and select from the menu.
This setting is only applicable for double digital input
points.
Open Name
Specify the name displayed when this DI is in the open
state:
• Single Point Digital Input - Open state = 0
• Double Point Digital Input - Open state = 1
The name can be entered manually, or double-click and
select from the menu. This name appears in this
application's user interface and HMI. It is also recorded in
the Historic Database.
Close Name
Specify the name displayed when this DI is in the close
state:
• Single Point Digital Input - Close state = 0
• Double Point Digital Input - Close state = 1
The name can be entered manually, or double-click and
select from the menu. This name appears in this
application's user interface and HMI. It is also recorded in
the Historic Database.
Value (3)
Specify the name of this digital input when it has a value
Name
of 3.
The name can be entered manually, or double-click and
select from the menu.
Value (3) Name is only applicable for double digital input
points.
Historical settings
Note: The D20E does not currently support the Historical data settings.
Event settings
Reference
Specify a text string that combines the bay name, group
Name
name, and provider name from the General tab.
COS Event
Specify when a change-of-state event is generated for
this digital input pseudo point.
Control settings
Reference
Specify a text string that combines the bay name, group
Name
name, and provider name from the General tab.
Open DO
Specify a DO point which is to trip (i.e., turn off) this DI
Point
when a control is applied to this point.
Close DO
Specify a DO point which is to close (i.e., turn on) this DI
Point
when a control is applied to this point.
Providers - Protocol settings
Reference
Specify a text string that combines the bay name, group
Name
name, and provider name from the General tab.
Physical Index Specify the index of the physical IO pin.
Debounce
Specify (in ms) the amount of time a point must stay in a
Filter Length
given state before a change to state is recorded.
Chatter Filter
Select the amount of time (in ms) to be used in the
Time Range
Chatter Filter calculation.
Chatter Filter
Specify the number of changes during the Chatter Filter
On Trigger
Time period that enables the Chatter Filter.
The recommended value is 10 to 20 changes, to reduce
event noise.
GE INFORMATION
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
Range
Disable
Off State Only
One State
Only
On and Off
State
0 (off) to
1000.ms
100 ms
1000 ms
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Default
Disable