CHAPTER 3: CONFIGURING THE D20E FIRMWARE

Configuring points

Digital input points

Single and double digital input

D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
The following sections provide details for configuring the D20E firmware with the following
point types:
Digital input points
on page 55
Counter points
on page 60
Analog input points
on page 63
Control output points
The DAPserver Studio tool is used to configure the D20E modules. Most of the
configuration information provided in this chapter is associated with the DAPserver Studio
Settings > Provider tab.
The D20E-S module allows up to 64 status input connections and the D20E-C module
allows up to 16 digital inputs.
There are up to 64 status inputs that can be configured as:
Single point status (see Table 4) or
Double point status (see Table 5).
When a status input is configured as a double point, each point occupies two input spaces
on termination block TB2; for example, on the D20E-S, TB2-1 and TB2-67 represent DI#1
LSB state; and TB2-2 and TB2-68 represent DI#1 MSB state. When mapping the double
point into DAP server, you only map the LSB.
Table 4: Single Input States:
State
Input
Off/Open
0
On/Close
1
Table 5: Double Input States:
State
Input
Off/Open
0
Transition
0
On/Close
1
Invalid
1
The D20MX Substation Controller does not support double Digital Input from the D20E IO
Module.
on page 69
1
0
0
1
GE INFORMATION
55