Bosch SDI2, B930 - ATM Style Alphanumeric Keypad Installation Manual

Bosch SDI2, B930 - ATM Style Alphanumeric Keypad Installation Manual

Advertisement

Bosch SDI2, B930 - ATM Style Alphanumeric Keypad Installation Manual

Overview

B930 keypads are SDI2 bus compatible devices. Each keypad has user adjustable options such as volume and display brightness, and an LCD display that shows five-line system messages.

B930 keypads connect to the SDI2 bus on the control panel using terminal wiring. You can connect more than one keypad to the control panel by wiring them in parallel.

You can program, diagnose, and troubleshoot the system from the control panel keypad as well as remotely through Remote Programming Software (RPS).
Keypad base overview

Callout ― Description
1 ― Wall mount holes
2 ― Single gang box holes
3 ― Double gang box holes
4 ― Wire opening
5 ― Surface mount wire openings
6 ― Gang box holes (3-4 in)
7 ― Surface mount wire channel
8 ― Bubble level
9 ― SDI2 wiring terminal block
10 ― Wire tie posts

SDI2 address switches

Two switches determine the address for the keypad. The control panel uses the address for communications. Use a slotted screwdriver to set the switches.

Access the address switches

  1. Unlock the keypad by turning the lock counter-clockwise. Refer to Figure 2.1.
    Unlocking the keypad
  2. Hold the keypad by the base in one hand. With the other hand, gently push down on the keypad to remove it from the base. Refer to Figure 2.2.
    Removing teh keypad
  3. Look at the back of the keypad, and locate the switches. Refer to Figure 2.3
    Switches locations
Callout ― Description
1 ― Address switches

Set the address switches

Set the address switches per the control panel configuration. If multiple SDI2 keypads reside on the same system, each SDI2 keypad must have a unique address. For single-digit addresses 1 through 9, set the tens switch to 0. Figure 2.4 shows the address switch setting for address 1.
Address switches

Installation

After you set the address switches for the proper address, mount the keypad base, wire to the control panel, and attach the keypad to the base.


Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.

Mount the keypad

You can surface mount the keypad, or mount it to standard electrical boxes, including single gang boxes.

Mounting the keypad:

  1. Use the base as a template to mark the desired mounting surface. Refer to Figure 1.1 for mounting hole and wiring locations.
  2. Pull the wiring through the desired wire opening in the base.
  3. Use the appropriate mounting hardware (supplied) to mount the base to the desired mounting surface. Refer to Figure 1.1 for mounting hole and wiring locations.

Wire to the control panel

When you wire the keypad to a control panel, use the control panel terminals labeled R, Y, G, B (PWR, A, B, COM). Connect them to the keypad terminals labeled R, Y, G, B. Refer to Figure 3.1.
Wiring the keypad to the SDI2 bus connection

Callout ― Description
1 ― Control panel
2 ― Terminal wiring
3 ― Keypad's SDI2 wiring terminal block

You can connect keypads to the SDI2 data bus by parallel wire run from the control panel to each keypad, wire from keypad to keypad, or a combination of the two techniques. Refer to Figure 3.2.
Installing multiple keypads using the SDI2 terminals

Reconnect the keypad to the base by sliding the keypad onto the base (reverse of Step 2). The keypad automatically locks onto the base. Apply power to the system.

Display

You can adjust the keypad's display brightness level, and you can turn the keypad's nightlight feature on or off.

Adjusting the keypad display brightness:

  1. Press [MENU] to open the Main menu.
  2. Use [NEXT] to go to the Press 5 for Settings Menu option, or simply press [5].
  3. Use [NEXT] to go to the Press 4 for Keypad Config option, or simply press [4].
  4. Press [1] to adjust the brightness.
  5. Use [PREV] or [NEXT] to adjust the brightness level. The changes apply immediately.
  6. Press [ESC] to exit the menu.

Turning the keypad nightlight on or off (control panel version 2.01 or higher):

  1. Press [MENU] to open the Main menu.
  2. Use [NEXT] to go to the Press 5 for Settings Menu option, or simply press [5].
  3. Use [NEXT] to go to the Press 4 for Keypad Config option, or simply press [4].
  4. Use [NEXT] to go to the Press 4 for Nightlight option, or simply press [4].
  5. Use [PREV] or [NEXT] to toggle between the Yes and No options.
  6. Press [ENTER] while viewing the desired option to save the programming.
  7. Press [ESC] to exit the menu.

Status indicators

You can diagnose and troubleshoot the system using the keypad's status indicators. Refer to Table 5.1.

Table 5.1: Keypad status indicators

Status indicator Function
Ready to turn on (arm)
Turned on (armed)
warning System trouble
GAS Gas alarm
AC power present

Audible tones

The keypad has a built-in speaker that produces several distinct warning tones. The keypad backlight illuminates when it emits an audible tone.

Table 6.1: Keypad audible tones

Tone Description
Fire alarm When an area is in fire alarm, the keypad emits a pulsed, high-pitched bell tone.
Gas alarm When a gas point activates, the keypad emits a unique high pitched tone.
User alarm When a user alarm (such as panic and medical alarms) occurs, the tone sounds for the programmed amount of time.
Burglary alarm When an area is in alarm, the keypad emits a steady, high pitched bell tone.
Entry delay The keypad emits an intermittent beep tone during entry delay periods to remind the user to disarm the area.
Exit delay The keypad emits an intermittent beep tone during exit delay.
Invalid button buzz When an invalid button, or sequence of buttons, is pressed, the keypad emits a flat buzz tone.
Keypress The keypad emits a muted beep tone as each button is pressed to indicate that the entry was accepted.
Trouble When a trouble event occurs, such as a service alert, the keypad emits a two-tone warble until you enter a programmed passcode with the appropriate authority.
Watch point fault A single clean tweedle tone alerts the user anytime a watch point is faulted.

Supervision

The control panel supervises all keypads on the SDI2 bus. If a supervised keypad fails to respond to the control panel, the control panel declares a Missing Keypad Trouble. When the control panel can again communicate with the keypad, it restores the Missing Keypad Trouble. During a Missing Keypad Trouble, any connected keypad that maintained contact with the control panel shows the Missing Keypad Trouble as its idle text, and shows the missing keypad's address. The communicating keypads also sound a trouble tone. Users can silence the trouble tone. If no other troubles exist, the tone silences when the missing keypad restores.

Show the firmware version

Showing the keypad firmware version:

  1. Remove the keypad from the base to remove power to the keypad. Refer to Figures 2.1 and 2.2.
  2. Return the keypad to the base to restore power.

The keypad shows the model number, keypad address, and firmware version for 10 seconds.

information
NOTICE!
You can also view a keypad's firmware version in RPS.

Use a soft cloth and non-abrasive cleaning solution to clean your keypad (for example, microfiber cloth and eyeglass cleaner). Spray the cleaner onto the cloth. Do not spray cleaners directly onto the keypad.

Keypad cleaning

Use a soft cloth and non-abrasive cleaning solution to clean your keypad (for example, microfiber cloth and eyeglass cleaner). Spray the cleaner onto the cloth. Do not spray cleaners directly onto the keypad.

Specifications

Dimensions 6.2 in x 4.7 in x 1 in (158 mm x 120 mm x 26 mm)
Voltage (input) 12 VDC nominal
Current 35 mA in standby mode 80 mA in alarm mode
Operating temperature 0°C to +50°C (+32°F to +122°F)
Relative humidity 5% to 93% at +32°C (+90°F) noncondensing
Terminal wire size 12 AWG to 22 AWG (2 mm to 65 mm)
SDI2 wiring Maximum distance - wire size (unshielded wire only):
1000 ft (305 m) - 22 AWG (0.65 mm)
Compatibility B9512G/B9512G-E
B8512G/B8512G-E
B6512
B5512
B4512
B3512
D9412GV4 version 2.0 and higher
D7412GV4 version 2.0 and higher
(Refer to the control panel installation document for number of supported devices.)

Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450 USA
www.boschsecurity.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Bosch SDI2, B930 - ATM Style Alphanumeric Keypad Installation Manual

Advertisement

Need Assistance?

Do you have a question about the SDI2 that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents