Honeywell 800 Series Manual page 7

Signal processor and viewing head
Table of Contents

Advertisement

Viewing Head Connector and
Wiring
Viewing heads are wired to the appropriate terminals
located on bottom of the 700ACSP, 700DCSP, P531 or
P532 signal processors. The terminals are listed
functionally in Table 2.
Table 2. Terminal Descriptions.
700ACSP or
P531 or
700DCSP
P532
Terminal
Terminal
VH SIG
VH3 SIG
VH SC
VH3 SC
VH +V
VH3 +V
VH GND
VH3 GND
Connectors and cables are shown in Fig. 3, Fig. 4, and Fig.
5. Fig. 3 shows the viewing head cable with the 1/2 in. NPT
pipe fitting and pigtail for use in a conduit. The PF model
comes with 10 feet of Honeywell C330S cable. This cable
is recommended for all new installations. It has ITC and
CIC ratings for hazardous location. Figs. 4 and 5 describe
the C330S cable used with the right angle field-wireable
connector. Refer to "Accessories" on page 11 for part
numbers.
S70x/S80x Viewing Head
Hazardous Location Installation of
Cables and Connectors
WARNING
EXPLOSION HAZARD
DO NOT CONNECT OR DISCONNECT THIS
EQUIPMENT UNLESS POWER HAS BEEN
REMOVED OR THE AREA IS KNOWN TO BE
NONHAZARDOUS.
SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
Description
Flame Signal from Viewing
Head
Shutter Drive Signal to Viewing
Head
+24VDC Power to Viewing Head
GND Signal Ground
AVERTISSEMENT
RISQUE D'EXPLOSION
NE PAS DEBRANCHER TANT QUE LE CIRCUIT EST
SOUS TENSION, A MOINS QU'lL NE S'AGISSE
D'UN EMPLACEMENT NON DANGEREUX.
LA SUBSTITUTION DE COMPOSANTS PEUT
RENDRE CE MATÉRIEL INACCEPTABLE POUR
LES EMPLACEMENTS DE CLASSE I, DIVISION 2.
The S70x/S80x viewing heads must be installed with a
connector and cable assembly that maintains the ingress
protection at the S70x/S80x viewing head. Additionally,
ITC/CIC approved cable installed in cable tray, or ITC/CIC
approved cable in metal conduit must be used between
the S70x/S80x and Signal Processor. Pre-assembled
connector/cable assemblies are listed below that provide
the proper seal at the viewing head, and meet ITC/CIC
approvals. A field wire-able connector that provides a
proper seal at the viewing head, along with ITC/CIC rated
raw cable are also available and listed below. The cable
installation must conform to the latest version of the
National Electric Code, or Canadian Electrical Code for
Class I, Division 2 hazardous locations.
Additionally, the connector must be secured as follows:
hand-tighten the connector at viewing head, until it can
no longer be turned. Continue tightening the connector an
additional 180 degrees using pliers, or similar tool.
WARNING
Over-tightening the connector can damage the
connector or housing.
Damage will void warranty and hazardous location
approvals. Do not exceed 180 degrees of further
rotation after hand tightening!
Verify that connector cannot be loosened by hand. This is
required for hazardous location installations.
ASY782 - Pre-assembled connector with led indicators
and 50 foot cable assembly, IP67 rated with CIC/ITC
approved cable.
ASY785 – Pre-assembled connector with led indicators
and 50 foot cable assembly, IP67 rated with CIC/ITC
approved cable.
ASY785-200 – Pre-assembled connector with led
indicators and 200 foot cable assembly, IP67 rated with
CIC/ITC approved cable.
C330S – ITC/CIC rated 4 conductor 22g cable with drain
wire, and overall shield.
ASY786 – Field wireable connector with led indicators ,
IP67 rated.
7
66-2069EP—08