HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD

SAFETY MANUAL: 700 SIGNAL PROCESSOR

700ACSP, 700DCSP Product Declaration
FIT FOR USE IN A LOW DEMAND SAFETY APPLICATION.
Models: 700ACSP & 700DCSP
Models
SIL
700AC
3
700DC
3
System Architecture
MTTR (Mean Time to Restoration
Proof Test Interval
Fit for use in
Term
Dangerous Failure
Safety-related System
Safety Function
Proof Test
MTTR (Mean Time to
Restoration)
sd
su
dd
du
HFT
System Architecture
PFD
(Average
AVG
Probability of Failure on
Demand)
FIT (Failures in Time)
Safety Function of the 700
The safety function of the 700 signal processor consists of
a Flame Relay which comprises its safety function and
behaves as follows:
The Flame Relay (Normally Open)
66-2069EP—08
HFT
SFF
0
>99%
0
>99%
Table 5. Definitions.
Failure which has the potential to put the safety-related system in a hazardous or fail-to-
function state.
A system that implements the required safety functions required to achieve or maintain a
safe state and is intended to achieve on its own or with other systems the necessary safety
integrity for the required safety functions.
Defined function, which is performed by a safety-related system with the aim of achieving
or maintaining a safe state for the plant, in respect of a specified hazardous event.
Periodic test performed to detect failures in a safety-related system so that, if necessary,
the system can be restored to an "as new" condition or as close as practical to this
condition.
The average duration required for restoration of operations after a failure.
Rate of safe detectable failures per one billion hours.
For example if 
= 3000, then it is estimated that there will be about 3,000 safe detectable
sd
failures during every one billion hours of operation.
For 
= 3000, this is about one safe detectable failure every 38 years.
sd
Rate of safe undetectable failures per one billion hours.
Rate of dangerous detectable failures per one billion hours.
Rate of dangerous undetectable failures per one billion hours.
Hardware Fault Tolerance
Specific configuration of hardware and software elements in a system.
Average Probability of Failure on Demand. In this case, regarding the 700 Signal Processor.
A unit of measurement representing one failure per billion hours. 1,000,000,000 hours is
approximately 114,155.25 years.
PFD
s
-4
1.79 x 10
1.93 x 10
-4
1.79 x 10
1.36 x 10
1oo1
8 hours
5 years
SIL 3 environment
Definition
• The Flame Relay will be energized when the signal
processor is powered and a flame on condition is
detected.
• The Flame Relay will be de-energized when the signal
processor is powered, a flame of condition is detected,
and the FFRT (Flame Failure Response Time) has
elapsed.
36
dd
-6
-9
8.53 x 10
-6
-9
8.53 x 10
du
-9
8.20 x 10
-9
8.20 x 10