Honeywell 800 Series Manual page 33

Signal processor and viewing head
Table of Contents

Advertisement

SETTING FLAME FAILURE RESPONSE
TIME (FFRT)
FFRT
1/2/3 SEC
PRESS, FFRT,
OPTION
FOR 2 SECONDS
2 SECS
IS THE PANEL LOCKED?
N
INCREASE
USE INCREASE OR DECREASE KEYS
TO ADJUST SETTING
DECREASE
Fig. 25. Flow Chart 7: Flame Failure Response Time (FFRT) Setup.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
DISPLAY SHOWS CURRENT
SETTING IN SECONDS
INCREASE
USE INCREASE OR DECREASE KEYS
TO ADJUST SETTING
DECREASE
Y
DISPLAY SHOWS 'PL',
UNTIL KEY RELEASED
STORE
RESET
rE
33
PRESS STORE TO SAVE
THE NEW SETTING
OR
PRESS RESET OR WAIT 4 SECONDS
TO RESTORE OLD SETTING
NORMAL OPERATION