Download Print this page

GE IC695ETM001-HW Manual page 7

Ethernet interface module

Advertisement

RX3i Ethernet Interface Module IC695ETM001-HW IPI
March 2016
New Features and Enhancements in This Release
None
Problems Resolved by This Release
Subject
In RX3i Ethernet firmware 6.40, an issue was introduced where an ETM001 will
Redundant IP
continue to respond to the redundant IP address even after it is switched to backup
does not work
mode. This problem has been corrected in firmware version 6.41.
properly in FW
6.40
This problem does NOT exist on RX3i ETM firmware versions prior to 6.40.
Release History
Catalog Number
IC695ETM001-HW
IC695ETM001-HV
IC695ETM001-HU
IC695ETM001-HU
IC695ETM001-GT
Release History
Firmware
Version
Date
6.41
Mar 2016
6.40
Feb 2016
6.31
Nov. 2015
Firmware
Nov. 2014
6.30
Boot 3.71
6.30
Nov. 2014
Description
Comments
In RX3i Ethernet firmware 6.40, an issue was introduced
where an ETM001 will continue to respond to the
redundant IP address even after it is switched to backup
mode. This problem has been corrected in firmware
version 6.41.
This problem does NOT exist on RX3i ETM firmware
versions prior to 6.40.
An enhancement was made to prevent the module from
becoming unresponsive and requiring a power cycle if it
was subjected to heavy network storm traffic. Reference:
GE Security Advisory is GE15-09, titled Network Storm
Denial of Service
In addition to the enhancement there were issues resolved.
Please refer to the "Problems Resolved by This Release"
section (above) for more details.
Firmware release 6.31 (IC695ETM001-HU) provides a Field
Upgrade Kit to address an issue identified with
IC695ETM001-GT where the module can unexpectedly go
into firmware update mode (Ethernet OK, LAN OK, and Log
Empty LEDs blink in unison). While in firmware update
mode, the module is unresponsive to Ethernet traffic
This hardware release (IC695ETM001-HU) addresses an
issue identified with IC695ETM001-GT where the module
can unexpectedly go into firmware update mode (Ethernet
OK, LAN OK, and Log Empty LEDs blink in unison). While in
firmware update mode, the module is unresponsive to
Ethernet traffic
This hardware release addresses a component
obsolescence issue. There are no changes to form, fit, or
function.