7-2. Applied Control of Outdoor Unit

The outdoor fan high static pressure support and priority operation mode setting (cooling / heating / number of
units / or priority indoor unit) functions are available by setting relevant switches provided on the interface P.C.
board of the outdoor unit.

7-2-1. Outdoor Fan High Static Pressure Shift

Setup
Change the outdoor DN code. (O.DN [019]) into "Outdoor Fan High Static Pressure operation."
This function must be enabled with every discharge duct connected outdoor unit.
Purpose/characteristics
Outdoor DN Code
(O.DN) Setting Operation
O.DN [019] = 0000
O.DN [019] = 0001
Specifications
Increase the speed of the propeller fan units on the outdoor fan to allow the installation of a duct with a maximum
external static pressure not greater than specified in the table below. If a discharge duct with a resistance greater
than 15 Pa (1.5 mmAq) is to be used, enable this function. The maximum external static pressures of single units
are shown below (Table 1).
Table 1: Maximum External Static Pressures of Single Outdoor Units
Model
Maximum external static pressure
(
) Outdoor unit air flow
) Calculate duct resistance from outdoor unit air flow.
(✱
0000 : Usual
0000 : None
0000 : mode 1 (50 dB)
0002 : mode 3 (44 dB)
0000 : System abnormal stop
0000 : System continuous operation
(Stop the corresponding indoor unit.)
0000: Usual
0000: TCC-Link
Operation
Normal operation
Outdoor Fan High Static Pressure operation
MCY-MUG
0401*
(Pa)
20
3
72
(m
/min)
0001 : High Static Pressure
Operation
0001 : Standby
0001 : mode 2 (47 dB)
0001 : System continuous operation
(Stop the corresponding indoor unit.)
0001 : System abnormal stop
001: Low frost operation
0003 : TU2C-Link
0501*
0601*
20
20
75
75
54
0000 : Usual
0000 : None
0000 : mode 1
0000 : System
abnormal stop
0000 : System
continuous
operation (Stop
the corresponding
indoor unit.)
0001: Mode 1
0000: TCC-Link