No.
Part
5
Clamp filter
for earth wire
(ZCAT3035-1330)
6
Coil-PMV
Work procedure
1. Detachment
1)Perform work of procedure 1-1 Detachment.
(Electrical control box cover)
2)Remove the clamp filter from the earth wire.
2. Attachment
1)Make two turn on the earth wire and attach the
clamp filter to it.
To prevent the clamp filter from opening,
securely fit the two claws on it.
2)Attach the electrical control box cover.
(Refer to 1. of 2 Attachment)
1. Detachment
1)Perform work of procedure 1. -1) (Electrical
control box cover) and 4. -1) (Top plate).
2)Remove the PMV wire from the wire clamp as
appropriate.
3)Disconnect the PMV wire connector from the
control P.C. board.
4)Remove the Coil-PMV.
2. Attachment
1)Fix the Coil-PMV assembly as before.
Rotate the Coil-PMV to lock the Body-PMV
by mating the protrusions of the Body-PMV
with the holes in the Coil-PMV.
When performing this task, the Coil-PMV
wires should be oriented to the right as
viewed from the control box.
Hole
Protrusion
2)Connect the wires disconnected as before.
3)Attach wire clamps to the PMV wires as before.
4)Attach the electrical control box cover and the
top plate. (Refer to 1. -2) and 4. -2)).
PMV wire direction
Rotate
245
Remarks
Clamp filter
2 turn
Wire clamp
Right
Control box
Lock