NOTE)
The individual test operation returns to the normal operation after 60 minutes.
• The test run is a forced run that ignores the set temperature. Be sure to stop the test run after work, paying
attention to the room temperature.
• After 60 minutes, the test run will be completed to protect the equipment, and the normal operation will be started
according to the set temperature. However, if there is no remote controller less setting is set, some indoor models
will not complete the test run even after 60 minutes have passed.

8-7-3. Check Code Clearing Function

(1)Clearing from the main remote controller
<RBC-ASCU11*>
Clearing a check code of the outdoor unit
There is no such function in the remote controller.
1
Push the [OFF timer] button for over 10 seconds.
2
Each time the [ ] or [ ] button is pushed, the recorded troubleshooting history is displayed in
sequence.
3
Push the [menu] button for over 10 seconds, doing so deletes the entire troubleshooting history
of the indoor unit.
4
After you have finished checking, push the [ON/OFF] button to return to normal mode.
3
1
2