Connection Of Cc-Link Dedicated Cable - Mitsubishi Electric FR-E720-0.1KNC Instruction Manual

Table of Contents

Advertisement

Wiring for CC-Link communication
(4)
Crimping the plug cover
Push the plug cover onto the plug with a tool such as pliers. After crimping, check that the plug cover is
securely snapped into the plug as shown in the right figure.
REMARKS
Misaligned latches between the plug cover and the plug may keep the cover lifted. The plug cover is not sufficiently crimped in
this condition. Push the plug cover until it snaps into the plug.
4.3.4

Connection of CC-Link dedicated cable

(1)
Connection to the connector
Connect the CC-Link dedicated cable to the CC-link communication connector
(2)
Grounding (earthing) the CC-Link dedicated cable
Use an M4 screw and a conduction area of a P-clip (enclosed item) to ground (earth) shielding wires of the CC-Link dedicated
cable to a position (as close as possible to the inverter) on the enclosure.
Take caution not to subject the CC-Link communication connector to stress.
CC-Link dedicated cable
loose slack
Take caution not to subject the cables to stress.
After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction.
52
CC-Link
dedicated cable
Enclosure
(inverter mounting surface)
Shield
P-clip
CAUTION
CC-Link
communication
connector
Resin part Conduction part
10.7
4.3
(14.7)

Advertisement

Table of Contents
loading

Table of Contents