Control mode
5.5.1

Changing the control method (Pr. 80, Pr. 81, Pr. 800)

Set when selecting the control method for Advanced magnetic flux vector control and General-purpose magnetic flux
vector control. The initial value is V/F control.
Select a control mode using Pr. 800 Control method selection.
Parameter
Name
Number
80
Motor capacity
81
Number of motor poles
Control method
800
selection
∗ Set a value other than "9999" in Pr. 80 and Pr. 81.
(1)
Setting of the motor capacity and the number of motor poles (Pr. 80, Pr. 81)
Motor specifications (motor capacity and number of motor poles) must be set to select Advanced magnetic flux vector
control or General-purpose magnetic flux vector control.
Set the motor capacity (kW) in Pr. 80 Motor capacity and set the number of motor poles in Pr. 81 Number of motor poles.
(2)
Selection of control method
Select the inverter control method for V/F control, Advanced magnetic flux vector control, and General-purpose magnetic
flux vector control.
Pr. 80, 81
Other than 9999
9999
(Pr. 80, Pr. 81 initial value)
∗ Control method is V/F control regardless of the setting value of Pr. 800 when "9999" is set in Pr. 80 Motor capacity or Pr. 81 Number of motor poles.
(3)
Control method switching by CC-Link communication (X18 signal)
Use the V/F switchover signal (X18) to change the control method (between V/F control and Advanced magnetic flux
vector control (General-purpose magnetic flux vector control)) with CC-Link communication.
Turn the X18 signal ON to change the currently selected control method (Advanced magnetic flux vector control or
General-purpose magnetic flux vector control) to V/F control.
To input the X18 signal to a virtual terminal of CC-Link communication, set "18" in one of Pr. 180 to Pr. 184 (input terminal
function selection).
REMARKS
Switch the control method using X18 signal during an inverter stop. If control method between V/F control and Advanced
(General-purpose) magnetic flux vector control is switched during the operation, the actual switchover does not take place until
the inverter stops. In addition, if control method is switched to V/F control during the operation, only second function becomes
valid as V/F control and second function are selected simultaneously in V/F control.
NOTE
Changing the assignment of a virtual terminal of CC-Link communication with Pr. 180 to Pr. 184 (input terminal function
selection) may affect other functions. Set parameters after confirming the function of each virtual terminal.
Parameters referred to
Advanced magnetic flux vector control
General-purpose magnetic flux vector control
Pr. 180 to Pr. 184 (input terminal function selection)
Pr. 450 Second applied motor
Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time
Pr. 46 Second torque boost
Pr. 47 Second V/F (base frequency)
Pr. 48 Second stall prevention operation current
Pr. 51 Second electronic thermal O/L relay
112
Initial
Setting Range
Value
9999
9999
20
Pr. 800 Setting
20
Advanced magnetic flux vector control
(Pr. 800 initial value)
30
General-purpose magnetic flux vector control
— ∗
Refer to page 114
Refer to page 117
Refer to page 163
Refer to page 144
Refer to page 113
Refer to page 126
Refer to page 120
Refer to page 142
0.1 to 15kW
Set the applied motor capacity.
9999
V/F control
2, 4, 6, 8, 10
Set the number of motor poles.
9999
V/F control
Advanced magnetic flux vector control ∗
20
V/F
General-purpose magnetic flux vector control ∗
30
control
Control Method
V/F control
Refer to page 135
Description