Monitor Display Selection Of Operation Panel (Pr. 52, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564) - Mitsubishi Electric FR-E720-0.1KNC Instruction Manual

Table of Contents

Advertisement

Monitor display and monitor output signal
5.14.2 Monitor display selection of operation panel
(Pr. 52, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564)
The monitor to be displayed on the main screen of the operation panel can be selected.
Parameter
Number
DU/PU main display data
52
∗1
selection
170
Watt-hour meter clear
171
Operation hour meter clear
Monitor decimal digits
268
∗1
selection
Energization time carrying-
563
over times
Operating time carrying-
564
over times
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 197)
∗1
This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
∗2
The setting values "56 and 57" are for manufacturer setting. Do not set.
(1)
Monitor description list (Pr. 52)
Set the monitor to be displayed on the operation panel in Pr. 52 DU/PU main display data selection.
Refer to the following table and set the monitor to be displayed.
Types of Monitor
Output frequency
Output current
Output voltage
Fault display
Frequency setting value
Motor torque
Converter output voltage
Regenerative brake duty
Electronic thermal relay function load
factor
Output current peak value
Converter output voltage peak value
Output power
Cumulative energization time
Actual operation time
,
1
∗2
Motor load factor
176
Name
Initial Value
0
(output
frequency)
9999
9999
9999
0
0
Pr. 52
Increment
Setting
0.01Hz
0/100
0.01A
0/100
0.1V
0/100
0/100
0.01Hz
5
0.1%
7
0.1V
8
0.1%
9
0.1%
10
0.01A
11
0.1V
12
0.01kW
14
1h
20
∗1
1h
23
0.1%
24
Setting Range
0, 5, 7 to 12, 14,
Select the monitor to be displayed on the
20, 23 to 25, 52 to
operation panel.
55, 61, 62, 100
Refer to the following table for monitor description.
∗2
0
Set "0" to clear the watt-hour meter monitor.
Sets the maximum value for the monitoring from
10
communication to 9999kWh.
Sets the maximum value for the monitoring from
9999
communication to 65535kWh.
Set "0" in the parameter to clear the operation time
0, 9999
monitor.
Setting 9999 does not clear.
0
Displayed as integral value
1
Displayed in 0.1 increments.
9999
No function
The numbers of cumulative energization time
0 to 65535
monitor exceeded 65535h is displayed. (Reading
(reading only)
only)
0 to 65535
The numbers of operation time monitor exceeded
(reading only)
65535h is displayed. (Reading only)
Displays the inverter output frequency.
Displays the inverter output current effective value.
Displays the inverter output voltage.
Displays 8 past faults individually.
Displays the set frequency.
Displays the motor torque in % on the assumption that the rated motor torque
is 100%. (Displays 0% during V/F control)
Displays the DC bus voltage value.
Brake duty set in Pr. 30, Pr. 70
Displays the thermal cumulative value on the assumption that the thermal
operation level is 100% (Larger thermal between the motor thermal and
transistor thermal).
∗4
Holds and displays the peak value of the output power monitor.
(Cleared at every start)
Holds and displays the peak value of the DC bus voltage value.
(Cleared at every start)
Displays the power on the inverter output side
Adds up and displays the energization time after inverter shipment.
You can check the numbers of the monitor value exceeded 65535h with Pr.
563.
Adds up and displays the inverter operation time.
You can check the numbers of the monitor value exceeded 65535h with Pr.
564.
Can be cleared by Pr. 171. (Refer to page 179)
Displays the output current value on the assumption that the inverter rated
current value is 100%.
Monitor value = output power monitor value/rated inverter current 100 [%]