Honeywell NOTIFIER INSPIRE E10 Operating Instructions Manual page 27

Fire alarm control panels
Hide thumbs Also See for NOTIFIER INSPIRE E10:
Table of Contents

Advertisement

How to put a detection Zone in test
01
Select the Menu icon
02
Select the 'Test Type' tab
03
Check the required Zone
04
Select the 'Proceed' button
The Outputs like Alarm devices, Voice Alarms and Fire Bridge link are not activated when a Zone is
placed in Test Mode.
05
Select the 'Start Test'
'Voice Alarm' and 'Fire Brigade' will be made inactivate during Zone test. Once a device is tested the 'Test
Number' is incremented by one. You can view details of the tested devices. On completion of a Zone test you
can
select the 'End Test' button to end Zone Test or move on to another Zone to test by selecting 'Edit
Test' and then check the required next Zone to test.
How to test the panels LEDs and Display
01
Select the Menu icon
2 password. Select 'Test Type' tab
02
Select the 'START INDICATOR TEST'
sounds and momentarily the screen colour will rotate between Green, Red and Blue.
03
To stop the test you must touch the screen and select the 'STOP INDICATOR TEST' button
test will automatically end the test after 15 seconds if left to continue.
and select 'Test System'
and then select 'Test Mode - Detection Test'
to put into Test. Note you can select multiple Zones.
.
button and note the 'Test' LED is lit and note the Outputs like 'Alarm Devices',
and then select the 'Test System'
.
button and observe all the LEDs on the panel are lit, the buzzer
INSPIRE E10/E15 Control Panels - Operating instructions
and then log in with your Access level 2 password.
button. and then log in with your Access level
.
. The indicator
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier inspire e15

Table of Contents