Installation
Mount the AXM on an EN50022 standard 7.5mm x 35mm
DIN rail or panel mount.
For DIN rail Mounting:
a. Holding the AXM with its top tilted in toward
the DIN rail, hook the two retaining tabs on the
back of the AXM onto the top of the DIN rail.
b. Push down and in to latch the two bottom
latching tabs of the AXM onto the DIN rail
—OR—
For Panel Mounting:
NOTE: The panel housing the AXM requires a ground bus that
connects to a suitable known ground. Ground the panel bus by
directly connecting to the closest point in the building's electrical
service grounding electrode system.
a. Open the AXM cover.
b. Use the mounting holes in the back cover to
attach it to the panel with appropriate fasten-
ers (not included). See Fig. 2.
To connect the AXM to a global controller:
1
Remove power from the VLX/ACM/AXM.
2
Connect AXM communications. Maintain polarity.
3
Connect power to the VLX/ACM/AXM.
Fig. 2
AXM controller dimensions in inches (mm).
© Honeywell
Fig. 3
Typical power connections for ACM and AXM. For
AXM BO power see Fig. 4.
Disposal
WEEE Directive 2012/19/EC Waste
Electrical and Electronic Equipment
directive
The product should not be disposed of
with other household waste. Check for the
nearest authorized collection centers or
authorized recyclers. The correct disposal
of end-of-life equipment will help prevent
potential negative consequences for the
environment and human health. Do not
burn this device.
Electrostatic sensitivity
The AXM and its components may be
susceptible to electrostatic discharge
(ESD). Use appropriate ESD grounding
techniques while handling the product.
When possible, always handle the product
by its non-electrical components.