Honeywell ALERTON AXM Installation Instructions
Honeywell ALERTON AXM Installation Instructions

Honeywell ALERTON AXM Installation Instructions

Advertisement

Quick Links

WARNING! Install all equipment in accordance with the National
Electric Code and in a manner acceptable to the local authority
having jurisdiction. Read these instructions and the AXM
Installation & Operations Guide carefully before installing
equipment. Failure to follow all instructions may result in
equipment damage or a hazardous condition.
ATTENTION! Installez tout le matériel en conformité avec le
Code national de l'électricité et d'une manière acceptable pour
l'autorité localecompétente. Lisez ces instructions et le guide d'
installation et fonctionnement de l'AXM avant l'installation du
matériel. Le non respect des instructions peut entraîner desdes
dommages matériels ou une situation dangereuse.
Overview
Control the AXM with a VLX or ACM with a Dual Port
EIA-485 Option Card. AXMs can be combined with EXPs.
Fig. 1
Typical AXM (I/O expansion module), AXM-1048 shown.
Mount the AXM in a clean, dry, indoor location, out of direct
sunlight, and avoid excessive vibration and electrical noise.
Keep temp. between 32 deg. F–131 deg. F (0 deg. C–55 deg.
C) and relative humidity between 0-95%, non-condensing.
The AXM, VLX and ACM can be mounted in separate
enclosures if the enclosures are immediately adjacent and
the AXM communications bus runs in conduit that does not
contain any high-voltage wiring.
Mount the AXM in any vertical or horizontal orientation.
Use single-point grounding and separate 24 VAC power for
the BO loads to help ensure proper grounding.
© Honeywell
Properly ground the panel, then terminate grounded
components of power, communications, and I/O wiring.
Power
Each AXM requires a 24 VAC, 50-60Hz, 20 VA minimum
power supply. Use a UL Listed transformer. VLXs, AXMs
and EXPs are half-wave devices so they may share an
appropriately sized transformer. Use a separate
transformer to power AXM and EXP BOs. AXM and EXP
power consumption ranges from 10 VA to 20 VA,
depending on the number and type of input devices
connected.
WARNING! The ACM is a full-wave device. All full-wave devices
must have a dedicated transformer.
WARNING! Half-wave and full-wave devices cannot share a
transformer or equipment damage will occur. If a VLX shares a
transformer with other devices, ensure all devices use a half-wave
rectifier.
WARNING! Do not share VLX/ACM/AXM/EXP power with any
VLC. VLCs require an independent 24 VAC power source.
WARNING! Do not connect 24 VAC terminals to ground or
equipment damage will occur. Maintain polarity of the power
connection among all devices sharing power.
Communications
AXMs communicate over a simple, twisted-pair
communications bus. Up to eight AXMs can connect to a
single global controller in a multi-drop configuration.
Universal inputs
Configure UIs to accept resistance (10K Ohm or 3K Ohm
thermistors or potentiometers), voltage (0-10VDC, 0-
5VDC), current (4-20mA), dry contact, solid-state switch
(transistor), or pulse-type inputs (IN-1, IN-2, and IN-3 only).
Outputs
Analog outputs support 4-20mA or 0-10VDC outputs.
Binary outputs; rated for 12VA (24VAC @ 0.5A). 20VDC
terminals can provide a power source up to 250mA total.
Page 1 - Printed in USA
Installation Instructions
LT-AXM-II-01
LT-AXM-II-01 Rev. 01
AXM

Advertisement

loading

Summary of Contents for Honeywell ALERTON AXM

  • Page 1  Mount the AXM in any vertical or horizontal orientation.  Use single-point grounding and separate 24 VAC power for the BO loads to help ensure proper grounding. LT-AXM-II-01 Rev. 01 © Honeywell Page 1 - Printed in USA...
  • Page 2 The AXM and its components may be susceptible to electrostatic discharge (ESD). Use appropriate ESD grounding techniques while handling the product. When possible, always handle the product by its non-electrical components. LT-AXM-II-01 Rev. 01 © Honeywell Page 2 - Printed in USA...
  • Page 3 Fig. 4 Typical power and BO connections for VLX and AXMs. © Honeywell Page 3 - Printed in USA LT-AXM-II-01 Rev. 01...