Honeywell Notifier FMM-1 Installation And Maintenance Instructions page 2

Monitor module

Advertisement

Figure 3. typical 2-Wire initiating circuit conFiguration, nFpa Style B or Security SySteMS:
NOTE: For UL Listed security installations, the FMM-1 must be mounted within the control panel enclosure.
ANY NUMBER OF UL LISTED CONTACT
CLOSURE DEVICES MAY BE USED. DO NOT MIX
FIRE ALARM INTIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
47K EOL
RESISTOR
ELR-47K
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 450µA MAX. @ 11 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
Figure 4. typical 4-Wire Fault tolerant initiating circuit conFiguration, nFpa Style d:
ANY NUMBER OF UL LISTED CONTACT
CLOSURE DEVICES MAY BE USED. DO NOT MIX
FIRE ALARM INTIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
EOL RESISTOR IS
INTERNAL AT
TERMINALS 8 & 9
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
NO-460-010
TO NEXT
DEVICE
MONITOR
MODULE
TO NEXT
DEVICE
MONITOR
MODULE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
2
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMENDED
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMENDED
FROM PANEL OR
PREVIOUS DEVICE
C0918-00
FROM PANEL OR
PREVIOUS DEVICE
C0919-02
I56-3506-001
©2007 Notifier